E E E EE E E FCU FCU vcd FCU vcd FCU FCU FCU vcdvcd vcd FCU FCU FCU FCU FCU E E FCU FCU FCU FCU FCU A B C D E F G H I K L M N O 1 2 3 4 5 6 7 8 300 x ...
11 downloads
25 Views
606KB Size
General Notes This drawing to be read in conjunction with all standard details and specifications. All dimensions to be verified on site. All works to comply with current building regulations.
NOTES:
2
1
3
4
5
6
7
1.
REFER TO STANDARD & PARTICULAR SPECIFICATIONS.
2.
ALL FIRE DAMPERS (FD) TO HAVE DUCT ACCESS PANEL.
8
VENTILATION LEGEND
250Ø GENERATOR FLUE & 130Ø CHP FLUE OFF-SET AND RISE TO ROOF LEVEL
CEILING MOUNTED EXTRACT GRILLE
CEILING MOUNTED EXTRACT GRILLE
A CEILING MOUNTED SUPPLY GRILLE
SMOKE FIRE DAMPER 25Ø CONDENSATE DROPS TO L/L & CONNECTS TO GLASSWASH WASTE
WATER TANK
VCD - VOLUME CONTROL DAMPER STORAGE
350x350 EXTRACT DUCT CONNECTS TO 350x250 SPIGOT ON CANOPY
300x300 CANOPY SUPPLY HEATER BATTERY
EG B1/1
350x350 PLANTROOM EXTRACT
AHU6 B1 KITCHEN SUPPLY
FCU A
FAN COIL UNIT A - 1150(l) x 620(w) x 200(h)
FCU B
FAN COIL UNIT B - 750(l) x 620(w) x 200(h)
FCU C
FAN COIL UNIT C - 950(l) x 620(w) x 200(h)
FCU D
FAN COIL UNIT D - 750(l) x 200(w) x 620(h) FLOOR MOUNTED
PLANT STAIR S01
300 x 300 B1 KITCHEN SUPPLY F/A TO H/L
250ø
620 x 620 x 306 FCU FCU D.6
EF5/AS SG B1/2
DUMB WAITER
PANTRY
LIFT L3
FCU B.6
E
B 250 X 150 SUPPLY DUCT
WALL MOUNTED UNIT FCU D.7.
350 X 350 B1 KITCHEN EXTRACT RISES T/A
SG B1/10
C
SG B1/11
250 X 150 EXTRACT DUCT FD
350Ø WASH-UP EXTRACT F/B 400Ø WASH-UP EXTRACT T/A
SG B1/15
FD 650x200
425x200
200ø
RISER FD
20Ø
200Ø EXTRACT AIR DUCT (GAS METER ROOM L/L VENT)
FD
200Ø EXTRACT AIR DUCT (GAS METER ROOM H/L VENT)
4-WAY BLOW CASSETTE 950(l) x 950(w) x 306(h) 950(l) x 950(w) x 264(h)
800 x 450 ACCESS PANEL 1200 x 450 ACCESS PANEL
E
900x200
300x250
RA B1/2
100mm LINEAR SLOT DIFFUSER
OUTLINE OF CEILING FEATURE. SEE ARCHITECT'S LAYOUT FOR EXACT LOCATION & DIMENSIONS. SEE NOTE *
vcd
200Ø
50mm LINEAR SLOT DIFFUSER
SG B1/16
150ø
RA B1/2
SG B1/12
250x200
4-WAY BLOW CASSETTE 620(l) x 620(w) x 306(h)
200Ø EXTRACT AIR DUCT (LAUNDRY)
450 x 450 ACCESS PANEL FOR BSV BOX (TYP.)
RA B1/1
250x300 2400 x 450 ACCESS PANEL
REFRIGERANT 3 PIPES CLIPPED TO CABLE TRAY
OUTLINE OF CEILING FEATURE. SEE ARCHITECT'S LAYOUT FOR EXACT LOCATION & DIMENSIONS. SEE NOTE *
VRF BRANCH SELECTOR BOX 388(l) x 326(w) x 207(h)
E
FCU
200 x 1150 x 620 FCU FCU D.1
REFRIGERANT 3 PIPES CLIPPED TO CABLE TRAY
FD FD
400 X 400 SUPPLY DUCT F/B TO H/L AHU1S/RS
RA B1/1
FCU
F
200 x 1150 x 620 FCU FCU D.5
E
EVENT SPACE
REFRIGERANT 2 PIPES CLIPPED TO CABLE TRAY
200ø
E
FD
FD
350x250
FCU
20Ø
300 X 250 B2 GENERAL EXTRACT F/B TO H/L
FD
RISER
FD
SG B1/4
D
300 X 250 TEF 1 B1/B2 MAINTENANCE EXTRACT F/B TO H/L
E
20Ø CONDENSATE CONNECTS TO 150Ø SVP VIA WATERLESS TRAP 400 X 400 EXTRACT DUCT T/B AHU1E/RS
STORE
RAS1
RAS1 800 x 100 RETURN AIR SLOT IN CEILING 0.075m2
RAS2
RAS2 900 x 150 RETURN AIR SLOT IN CEILING 0.120m2
FD
G FCU D.4
200ø
1200 X 400 FRESH AIR DUCT F/A & T/B DUCT OFFSETS WITHIN VOID RISER
500 x 500 ACCESS PANEL
200Ø
200ø
200ø 200x200
1000 X 400 FRESH AIR INTAKE DUCT F/A & T/B FIRE RATED.
EG B1/2
fcu moved slightly to allow access. Refrig. moved to left side of fcu
OUTLINE OF CEILING FEATURE. SEE ARCHITECT'S LAYOUTS FOR EXACT LOCATION & DIMENSIONS
EG B1/2
SF 3
250ø
RA B1/2 200x200 WC EXTRACT DROPS T/B WITH FD
WC
FD RISER
WC CORRIDOR
200 x 950 x 620 FCU FCU B.2
FCU
WC
SG B1/1
FIRE COMPARTMENT WALL TO BE OFF-SET ABOVE CEILING
E
vcd
PLENUM BOX
500 x 350 ACCESS PANEL
MEETING ROOM 2
OUTLINE OF CEILING FEATURE. SEE ARCHITECT'S LAYOUT FOR EXACT LOCATION & DIMENSIONS. SEE NOTE *
300x250
EG B1/2
20Ø
RA B1/2
EG B1/2
20Ø CONDENSATE DROPS TO L/L & CONNECTS TO SVP VIA WATERLESS TRAP
FCU
300x150
vcd
STAIR S02
200ø
IN-DUCT CROSS-TALK ATTENUATORS. CTA4
IN-DUCT CROSS-TALK ATTENUATORS. CTA2
FCU
EG B1/2
3. ACCESS PANEL FOR BSV BOXES TO BE ON THE CONTROL BOX SIDE. SITE TO CONFIRM CONTROL BOX SIDE ONCE INSTALLED.
WC
MEETING CORRIDOR
200 x 950 x 620 FCU FCU B.3
200ø
2. ACCESS PANEL FOR CASSETTE UNITS TO BE ON THE DRAIN, POWER UNIT & REFRIGERANT SIDE. SITE TO CONFIRM THE SERVICES SIDE ONCE INSTALLED.
WC
1000 X 400 FRESH AIR INTAKE DUCT DROPS T/B WITH FD IN SLAB
WC
4. SEE DETAIL DRAWINGS COR-217-MEP-PLN-013 TO 024 FOR ACCESS PANELS IN GUESTROOMS EG B1/2
100ø
OFFICE CORRIDOR
20Ø
EG B1/2
SG B1/20
300x150
WC
FCU
E
M
SG B1/19
200ø
1. SETTING OUT DIMENSIONS FOR ACCESS PANELS FOR FAN COIL UNITS/ CASSETTE UNITS, FANS, BSV BOXES, HEATER BATTERIES, FIRE DAMPERS & DOOR HEATER WILL BE DETERMINED FROM THE FINAL INSTALLATION POSITION OF THESE UNITS. SITE TO CONFIRM EXACT POSITIONS.
200x100
NOTES:
L
WC
STAIR LOBBY
FD 400 X 400 SUPPLY DUCT F/A TO H/L
SG B1/18
SG B1/14
SG B1/9
K
vcd
25Ø
SG B1/8
SG B1/7
500 x 350 ACCESS PANEL AT LL
FCU
200 x 1150 x 620 FCU FCU D.3
250ø
200ø
400x250
200ø
FCU
400x250
FCU
FCU
500x250
REFRIGERANT PIPEWORK CABLE TRAY 300mm
SG B1/17
RA B1/1
200 x 950 x 620 FCU FCU C.1
FCU SG B1/13
SG B1/6
CABLE TRAY LEGEND
200 x 950 x 620 FCU FCU C.2
300x250
20Ø
200 x 950 x 620 FCU FCU B.1
MEETING ROOM 1
200ø
FCU
200ø
I
FCU
FCU
EG B1/3
1000x250 SG B1/3 HB B1/1
IN-DUCT CROSS-TALK ATTENUATORS. CTA1
300x250
RA B1/1
H 200 x 1150 x 620 FCU FCU D.2
RA B1/1 RA B1/1
RA B1/1
300x150
20Ø
SG B1/5
IN-DUCT CROSS-TALK ATTENUATORS. CTA3
150ø
900x200
250x200
E
250x200
200ø
PRE-FUNCTION
200ø
FCU
vcd
100Ø WC EXTRACT 20Ø CONDENSATE CONNECTS TO 150Ø SVP VIA WATERLESS TRAP
E
* MEETING ROOMS/DND BAR FCU POSITIONS UNDER REVIEW WITH LSI CO-ORDINATION WITH FEATURE CEILING
350 X 350 PLANTROOM EXTRACT AIR DUCT F/B TO H/L
E
350 X 350 B1 KITCHEN EXTRACT
TEF1/AS
400x250
RISER
FCU
250x150
LIFT L1
FAN COIL UNIT A.1 - A.4 - 1150(l) x 620(w) x 200(h) FAN COIL UNIT A.6 - 700(l) x 620(w) x 200(h) FAN COIL UNIT B.1 - B.3 - 950(l) x 620(w) x 200(h) FAN COIL UNIT B.4 - 700(l) x 620(w) x 200(h) FAN COIL UNIT C.1 - C.2 - 950(l) x 620(w) x 200(h) FAN COIL UNIT D.1 - D.5 - 1150(l) x 620(w) x 200(h) FAN COIL UNIT M.1 - M.6 - 1150(l) x 620(w) x 200(h) FAN COIL UNIT 0.06 - 0.07 - 950(l) x 620(w) x 200(h)
1200Wx700H PLENUM
300x250
LIFT L2
LIFT L4
PLANT
200ø
350x350
800 x 800 B2 KITCHEN EXTRACT OFF-SETS & RISES T/A SEE RISER DETAIL
GYM
250x150
250ø
900 x 600 B2 EXTRACT DUCT F/B L/L
600Wx350H PLENUM
SERVICE CORRIDOR
250Ø SUPPLY AIR DUCTS CONNECT TO CANOPY SPIGOTS
200 x 700 x 620 FCU FCU B.4
300ø ACC. WC EG B1/2
200x150 MEETING ROOM 3
200x150
A4 A3
OUTLINE OF CEILING FEATURE. SEE ARCHITECT'S LAYOUT FOR EXACT LOCATION & DIMENSIONS. SEE NOTE *
Model
SLC
05-05-17
FCU D7. SHOWN IN STORE ROOM.
Engineer
RS
05-05-17
FCU B.5. & B.7. REFERENCED. REVIEW NOTE ADDED.
Checked
RS
05-05-17
ACCESS PANELS ADDED. NOTE ADDED.
Model
SLC
29-03-17
SUPPLY DUCTWORK REVISED IN EVENTS.
Engineer
RS
29-03-17
Checked
RS
29-03-17
Model
SLC
23-0217
Engineer
RS
23-0217
Checked
RS
23-0217
Model
SLC
19-01-2017
Engineer
RS
19-01-2017
Checked
RS
19-01-2017
FOR CONSTRUCTION APPROVAL
A2
RA B1/2
N
WALL MOUNTED AC UNIT/TRAY & REFRIG. PIPES FOR
FOR CONSTRUCTION APPROVAL
A1
20Ø CONDENSATE DROPS TO L/L & CONNECTS TO SVP WITH WATERLESS TRAP
Rev
SMOKE SHAFT
Description
Init
Date
CONSTRUCTION APPROVAL
WALL MOUNTED A.C. UNIT (1200Lx300Dx400H). FCU B.5 OFFICE/ADMINSTRATION
CEILING AC UNIT FCU B.7.
GM OFFICE
Cordant Projects Portland Road, Oak Green Earl Road, Stanley Green Business Park Cheadle Hulme, Cheshire. SK8 6QL (T) 0161 641 4941
O Client
FR HOLDINGS LTD. Project/Site Location
GARLICK HILL, EC4
Drawing Title
LEVEL -01 BASEMENT VENTILATION LAYOUT
Scale
1 : 50 Sheet Size
A0
Modelled
Engineer
Approved
PH
RS
RS
Drawing No.
COR-217-MV-PLN-002
Date
Oct'16 Revision
A4