Produced by Ansell Lighting Design Department Page 1/71Moxy Stratford plot Revision D 170824Moxy Stratford Revision D Installation : New Proposed Ligh...
5 downloads
18 Views
2MB Size
Moxy Stratford Revision D Installation : New Proposed Lighting Project number
: 99-29873-MR
Customer
: Cordant Technical
Processed by
: Mike Burgess
Date
: 24.08.2017
Project description: Calculation based on standard reflectances. Room/exterior area dimensions and floor to ceiling/mounting heights issued from wholesaler. PLEASE NOTE: All room/exterior area dimensions to be checked on-site prior to installation. Lighting designed to CIBSE guidelines where applicable and/or client requirements, all stated lux values are for overall averages across the room reference plane. Revision A ; 16/01/17 - all fittings to be self-test. Recessed fittings. Revision B ; 20/01/17 - Revise as per instruction from Ford Cornes - CHANGE TO FALCON LED ON STAIRS - KEEP RAVEN LED IN CORRIDORS, USE FALCON LED IN ALL OTHER AREAS - CHANGE STORMLOC COLOUR SO EASY TO DISTINGUISH - CENTRAL ROOM IS THE KITCHEN - CURRENT KITCHEN A CAR PORT ANSELL RECOMMED A LUX LEVEL OF 15 LUX AROUND THE HOB AREA IN THE KITCHEN. HOWEVER NO HOB AREA ON PLANS SO ANSELL HAVE DESIGNED TO STANDARD 0.5LUX ANSELL HAVE PLACED THE EMERGENCY REFERENCE PLANE FOR THE PLANT ROOM AT 0.75M FOR A STANDARD VISUAL TASK AREA AS NO PLANS OF PLANT ROOM RECEIVED ANSELL HAVE USED THE CENTURION LED IN THE PLANT ROOM INSTEAD OF THE FALCON LED DUE TO ITS HIGHER LUMEN OUTPUT. ASLED5 = DARK BLUE ASLED5/M3 = LIGHT BLUE ASLED2X5 = DARK GREEN ASLED2X5/M3 = LIGHT GREEN REVISION C ; 24/1/17 - NEW PLANS RECEIVED FOR PLANT ROOM, REMOVE WALL MOUNTED FITTINGS. ADD LINEAR FITTINGS BACK INTO LOADING BAY / DISABLED PARKING REVISION D ; 24/8/17 - REVISE CEILING HEIGHTS IN GROUND FLOOR LIFT LOBBY TO 3.5M AND ALL OTHER FLOORS TO 2.5M
The following values are based on exact calculations on calibrated lamps, luminaires and their arrangement. In practice, gradual divergences can occur. Guarantee claims for luminaire data are excluded. Relux and the luminaire manufacturers accept no liability for consequential damage and damage which is occasioned to the user or to third parties.
Produced by Ansell Lighting Design Department Moxy Stratford plot Revision D 170824
Page 1/71
Object Installation Project number Date
: : : :
Moxy Stratford Revision D New Proposed Lighting 99-29873-MR 24.08.2017
1
GROUND FLOOR
1.1
Description, GROUND FLOOR
1.1.1 Floor plan
N [m] 20
15
10
5
0
-5
-10
-15
0
5
10
15
20
25
30
35
40
45
50
[m] 1 : 250
Produced by Ansell Lighting Design Department Moxy Stratford plot Revision D 170824
Page 2/71
Object Installation Project number Date
: : : :
Moxy Stratford Revision D New Proposed Lighting 99-29873-MR 24.08.2017
1
GROUND FLOOR
1.1
Description, GROUND FLOOR
1.1.1 Floor plan
Wall x 1 29.94 m 2 30.03 m 3 31.63 m 4 31.55 m 5 34.20 m 6 38.15 m 7 52.17 m 8 42.10 m 9 42.10 m 10 14.77 m 11 14.77 m 12 0.34 m 13 0.34 m 14 0.00 m 15 0.00 m Floor Ceiling Room height Height of reference plane
y -14.90 m -14.74 m -15.55 m -15.71 m -17.02 m -9.19 m 22.71 m 22.70 m 22.00 m 22.00 m 21.60 m 21.61 m 1.20 m 1.20 m 0.00 m
Length 33.44 m 0.19 m 1.79 m 0.18 m 2.96 m 8.78 m 34.84 m 10.07 m 0.70 m 27.33 m 0.40 m 14.43 m 20.41 m 0.33 m 1.20 m
Reflectance 50.0 % 50.0 % 50.0 % 50.0 % 50.0 % 50.0 % 50.0 % 50.0 % 50.0 % 50.0 % 50.0 % 50.0 % 50.0 % 50.0 % 50.0 % 20.0 % 70.0 %
5.50 m 0.75 m
Produced by Ansell Lighting Design Department Moxy Stratford plot Revision D 170824
Page 3/71
Object Installation Project number Date
: : : :
Moxy Stratford Revision D New Proposed Lighting 99-29873-MR 24.08.2017
1
GROUND FLOOR
1.2
Summary, GROUND FLOOR
1.2.1 Result overview, LOADING BAY / DISABLED PARKING
N [m] 20
15
10
5
0
-5
-10
-15 0
Illuminance [lx]
75
5
10
15
20
100
25
Average indirect fraction 0.00 m 0.80
Total luminous flux of all lamps Total power Total power per area (1389.91 m²)
204084 lm 2178.6 W 1.57 W/m²
Eav Emin Emax Emin/Em Emin/Emax
35
150
General Calculation algorithm used Height of evaluation surface Maintenance factor
Illuminance Average illuminance Minimum illuminance Maximum illuminance Uniformity Uo Diversity Ud
30
40
45
200
50
[m]
300
136 lx 48 lx 188 lx 1:2.82 (0.35) 1:3.9 (0.26)
Type No.\Make
2
2
3
10
4
ANSELL - Emergency Order No. : !AE3LED/3M/W/ST+AE3LED/ALAR Luminaire name : EAGLE 3-IN-1 LED EXIT SIGN Equipment : 1 x / 124 lm ANSELL Order No. Luminaire name Equipment
: ASLED5 : Industrial - Stormloc IP65 LED Non-Corrosive : 1 x 36.6 W / 3800 lm
41
Order No. Luminaire name Equipment
: ASLED5/M3 : Industrial - Stormloc IP65 LED Non-Corrosive : 1 x 36.6 W / 3800 lm
7
14
Order No. Luminaire name Equipment
: ACELED/3M/ST : Emergency - Centurion LED Bulkhead : 1 x 6 W / 193 lm
12
38
Order No. Luminaire name Equipment
: !ACELED/3M/ST : Emergency - Centurion LED Bulkhead : 1 x 6 W / 193 lm(0%)
Produced by Ansell Lighting Design Department Moxy Stratford plot Revision D 170824
Page 4/71
Object Installation Project number Date
1.2
: : : :
Moxy Stratford Revision D New Proposed Lighting 99-29873-MR 24.08.2017
Summary, GROUND FLOOR
1.2.2 Result overview, STORE
N [m] 20
15
10
5
0
-5
-10
-15 0
Illuminance [lx]
75
5
10
15
20
100
25
Average indirect fraction 0.00 m 0.80
Total luminous flux of all lamps Total power Total power per area (1389.91 m²)
204084 lm 2178.6 W 1.57 W/m²
Eav Emin Emax Emin/Em Emin/Emax
35
150
General Calculation algorithm used Height of evaluation surface Maintenance factor
Illuminance Average illuminance Minimum illuminance Maximum illuminance Uniformity Uo Diversity Ud
30
40
45
200
50
[m]
300
148 lx 110 lx 170 lx 1:1.34 (0.74) 1:1.55 (0.65)
Type No.\Make
2
2
3
10
4
ANSELL - Emergency Order No. : !AE3LED/3M/W/ST+AE3LED/ALAR Luminaire name : EAGLE 3-IN-1 LED EXIT SIGN Equipment : 1 x / 124 lm ANSELL Order No. Luminaire name Equipment
: ASLED5 : Industrial - Stormloc IP65 LED Non-Corrosive : 1 x 36.6 W / 3800 lm
41
Order No. Luminaire name Equipment
: ASLED5/M3 : Industrial - Stormloc IP65 LED Non-Corrosive : 1 x 36.6 W / 3800 lm
7
14
Order No. Luminaire name Equipment
: ACELED/3M/ST : Emergency - Centurion LED Bulkhead : 1 x 6 W / 193 lm
12
38
Order No. Luminaire name Equipment
: !ACELED/3M/ST : Emergency - Centurion LED Bulkhead : 1 x 6 W / 193 lm(0%)
Produced by Ansell Lighting Design Department Moxy Stratford plot Revision D 170824
Page 6/71
Object Installation Project number Date
1.2
: : : :
Moxy Stratford Revision D New Proposed Lighting 99-29873-MR 24.08.2017
Summary, GROUND FLOOR
1.2.3 Result overview, STORE
N [m] 20
15
10
5
0
-5
-10
-15 0
Illuminance [lx]
100
5
10
15
20
150
25
Average indirect fraction 0.00 m 0.80
Total luminous flux of all lamps Total power Total power per area (1389.91 m²)
204084 lm 2178.6 W 1.57 W/m² (0.88 W/m²/100lx)
Eav Emin Emax Emin/Em Emin/Emax
35
200
General Calculation algorithm used Height of evaluation surface Maintenance factor
Illuminance Average illuminance Minimum illuminance Maximum illuminance Uniformity Uo Diversity Ud
30
40
45
300
50
[m]
500
178 lx 117 lx 226 lx 1:1.52 (0.66) 1:1.94 (0.52)
Type No.\Make
2
2
3
10
4
ANSELL - Emergency Order No. : !AE3LED/3M/W/ST+AE3LED/ALAR Luminaire name : EAGLE 3-IN-1 LED EXIT SIGN Equipment : 1 x / 124 lm ANSELL Order No. Luminaire name Equipment
: ASLED5 : Industrial - Stormloc IP65 LED Non-Corrosive : 1 x 36.6 W / 3800 lm
41
Order No. Luminaire name Equipment
: ASLED5/M3 : Industrial - Stormloc IP65 LED Non-Corrosive : 1 x 36.6 W / 3800 lm
7
14
Order No. Luminaire name Equipment
: ACELED/3M/ST : Emergency - Centurion LED Bulkhead : 1 x 6 W / 193 lm
12
38
Order No. Luminaire name Equipment
: !ACELED/3M/ST : Emergency - Centurion LED Bulkhead : 1 x 6 W / 193 lm(0%)
Produced by Ansell Lighting Design Department Moxy Stratford plot Revision D 170824
Page 8/71
Object Installation Project number Date
1.2
: : : :
Moxy Stratford Revision D New Proposed Lighting 99-29873-MR 24.08.2017
Summary, GROUND FLOOR
1.2.4 Result overview, STORE
N [m] 20
15
10
5
0
-5
-10
-15 0
Illuminance [lx]
50
5
10
15
20
75
25
Average indirect fraction 0.00 m 0.80
Total luminous flux of all lamps Total power Total power per area (1389.91 m²)
204084 lm 2178.6 W 1.57 W/m² (1.51 W/m²/100lx)
Eav Emin Emax Emin/Em Emin/Emax
35
100
General Calculation algorithm used Height of evaluation surface Maintenance factor
Illuminance Average illuminance Minimum illuminance Maximum illuminance Uniformity Uo Diversity Ud
30
40
45
150
50
[m]
200
104 lx 42 lx 158 lx 1:2.47 (0.41) 1:3.74 (0.27)
Type No.\Make
2
2
3
10
4
ANSELL - Emergency Order No. : !AE3LED/3M/W/ST+AE3LED/ALAR Luminaire name : EAGLE 3-IN-1 LED EXIT SIGN Equipment : 1 x / 124 lm ANSELL Order No. Luminaire name Equipment
: ASLED5 : Industrial - Stormloc IP65 LED Non-Corrosive : 1 x 36.6 W / 3800 lm
41
Order No. Luminaire name Equipment
: ASLED5/M3 : Industrial - Stormloc IP65 LED Non-Corrosive : 1 x 36.6 W / 3800 lm
7
14
Order No. Luminaire name Equipment
: ACELED/3M/ST : Emergency - Centurion LED Bulkhead : 1 x 6 W / 193 lm
12
38
Order No. Luminaire name Equipment
: !ACELED/3M/ST : Emergency - Centurion LED Bulkhead : 1 x 6 W / 193 lm(0%)
Produced by Ansell Lighting Design Department Moxy Stratford plot Revision D 170824
Page 10/71
Object Installation Project number Date
1.2
: : : :
Moxy Stratford Revision D New Proposed Lighting 99-29873-MR 24.08.2017
Summary, GROUND FLOOR
1.2.5 Result overview, STORE
N [m] 20
15
10
5
0
-5
-10
-15 0
Illuminance [lx]
75
5
10
15
20
100
25
Average indirect fraction 0.00 m 0.80
Total luminous flux of all lamps Total power Total power per area (1389.91 m²)
204084 lm 2178.6 W 1.57 W/m² (1.24 W/m²/100lx)
Eav Emin Emax Emin/Em Emin/Emax
35
150
General Calculation algorithm used Height of evaluation surface Maintenance factor
Illuminance Average illuminance Minimum illuminance Maximum illuminance Uniformity Uo Diversity Ud
30
40
45
200
50
[m]
300
127 lx 58 lx 187 lx 1:2.17 (0.46) 1:3.21 (0.31)
Type No.\Make
2
2
3
10
4
ANSELL - Emergency Order No. : !AE3LED/3M/W/ST+AE3LED/ALAR Luminaire name : EAGLE 3-IN-1 LED EXIT SIGN Equipment : 1 x / 124 lm ANSELL Order No. Luminaire name Equipment
: ASLED5 : Industrial - Stormloc IP65 LED Non-Corrosive : 1 x 36.6 W / 3800 lm
41
Order No. Luminaire name Equipment
: ASLED5/M3 : Industrial - Stormloc IP65 LED Non-Corrosive : 1 x 36.6 W / 3800 lm
7
14
Order No. Luminaire name Equipment
: ACELED/3M/ST : Emergency - Centurion LED Bulkhead : 1 x 6 W / 193 lm
12
38
Order No. Luminaire name Equipment
: !ACELED/3M/ST : Emergency - Centurion LED Bulkhead : 1 x 6 W / 193 lm(0%)
Produced by Ansell Lighting Design Department Moxy Stratford plot Revision D 170824
Page 12/71
Object Installation Project number Date
1.2
: : : :
Moxy Stratford Revision D New Proposed Lighting 99-29873-MR 24.08.2017
Summary, GROUND FLOOR
1.2.6 Result overview, PLANT ROOM
N [m] 20
15
10
5
0
-5
-10
-15 0
Illuminance [lx]
150
5
10
15
20
200
25
Average indirect fraction 0.00 m 0.80
Total luminous flux of all lamps Total power Total power per area (1389.91 m²)
204084 lm 2178.6 W 1.57 W/m²
Eav Emin Emax Emin/Em Emin/Emax
35
300
General Calculation algorithm used Height of evaluation surface Maintenance factor
Illuminance Average illuminance Minimum illuminance Maximum illuminance Uniformity Uo Diversity Ud
30
40
45
500
50
[m]
750
253 lx 170 lx 286 lx 1:1.49 (0.67) 1:1.68 (0.59)
Type No.\Make
2
2
3
10
4
ANSELL - Emergency Order No. : !AE3LED/3M/W/ST+AE3LED/ALAR Luminaire name : EAGLE 3-IN-1 LED EXIT SIGN Equipment : 1 x / 124 lm ANSELL Order No. Luminaire name Equipment
: ASLED5 : Industrial - Stormloc IP65 LED Non-Corrosive : 1 x 36.6 W / 3800 lm
41
Order No. Luminaire name Equipment
: ASLED5/M3 : Industrial - Stormloc IP65 LED Non-Corrosive : 1 x 36.6 W / 3800 lm
7
14
Order No. Luminaire name Equipment
: ACELED/3M/ST : Emergency - Centurion LED Bulkhead : 1 x 6 W / 193 lm
12
38
Order No. Luminaire name Equipment
: !ACELED/3M/ST : Emergency - Centurion LED Bulkhead : 1 x 6 W / 193 lm(0%)
Produced by Ansell Lighting Design Department Moxy Stratford plot Revision D 170824
Page 14/71
Object Installation Project number Date
: : : :
Moxy Stratford Revision D New Proposed Lighting 99-29873-MR 24.08.2017
1
GROUND FLOOR
1.3
Calculation results, GROUND FLOOR
1.3.1 Boundary line, LOADING BAY / DISABLED PARKING (E)
[m] 5.5 5.0 4.5 4.0 3.5 3.0 2.5 2.0 1.5 1.0 0.5 0.0 0
Illuminance [lx]
0.5
4
5
Required minimum illuminance Minimum illuminance Maximum illuminance Uniformity Height Calculation algorithm used Maintenance factor
2
6
8
10
10
15
12
[m] 1 : 100 20
: 0.5 lx Emin Emax Emin/Emax
: 0.5 lx : 7.8 lx : 1 : 16.30 (0.06) (Threshold value 1:40) :0m : Direct component : 0.8
Produced by Ansell Lighting Design Department Moxy Stratford plot Revision D 170824
Page 16/71
Object Installation Project number Date
1.3
: : : :
Moxy Stratford Revision D New Proposed Lighting 99-29873-MR 24.08.2017
Calculation results, GROUND FLOOR
1.3.2 Boundary line, STAIRS (E)
[m] 4.5
4.0
3.5
3.0
2.5
2.0
1.5
1.0
0.5
0.0 0.0
Illuminance [lx]
0.5
1
10
Required minimum illuminance Minimum illuminance Maximum illuminance Uniformity Height Calculation algorithm used Maintenance factor
1.0
1.5
2.0
20
2.5
3.0
[m] 1 : 25
30
40
: 1 lx Emin Emax Emin/Emax
: 1 lx : 2 lx : 1 : 1.89 (0.53) (Threshold value 1:40) :0m : Direct component : 0.8
Produced by Ansell Lighting Design Department Moxy Stratford plot Revision D 170824
Page 17/71
Object Installation Project number Date
1.3
: : : :
Moxy Stratford Revision D New Proposed Lighting 99-29873-MR 24.08.2017
Calculation results, GROUND FLOOR
1.3.3 Boundary line, STAIRS (E)
[m] 2.0 1.6 1.2 0.8 0.4 0.0 0
Illuminance [lx]
1
1
10
Required minimum illuminance Minimum illuminance Maximum illuminance Uniformity Height Calculation algorithm used Maintenance factor
2
3
4
20
5
6
[m] 1 : 50 30
40
: 1 lx Emin Emax Emin/Emax
: 2 lx : 5 lx : 1 : 2.51 (0.40) (Threshold value 1:40) :0m : Direct component : 0.8
Produced by Ansell Lighting Design Department Moxy Stratford plot Revision D 170824
Page 18/71
Object Installation Project number Date
1.3
: : : :
Moxy Stratford Revision D New Proposed Lighting 99-29873-MR 24.08.2017
Calculation results, GROUND FLOOR
1.3.4 Boundary line, STAIRS (E)
[m] 5.5
5.0
4.5
4.0
3.5
3.0
2.5
2.0
1.5
1.0
0.5
0.0 0.0 0.2 0.4 0.6 0.8 1.0 1.2 1.4 1.6
[m] 1 : 25
Illuminance [lx]
1
10
Required minimum illuminance Minimum illuminance Maximum illuminance Uniformity Height Calculation algorithm used Maintenance factor
20
30
40
: 1 lx Emin Emax Emin/Emax
: 1 lx : 3 lx : 1 : 2.83 (0.35) (Threshold value 1:40) :0m : Direct component : 0.8
Produced by Ansell Lighting Design Department Moxy Stratford plot Revision D 170824
Page 19/71
Object Installation Project number Date
1.3
: : : :
Moxy Stratford Revision D New Proposed Lighting 99-29873-MR 24.08.2017
Calculation results, GROUND FLOOR
1.3.5 Boundary line, CIRCULATION (E)
[m] 3.0 2.5 2.0 1.5 1.0 0.5 0.0 0
Illuminance [lx]
2
1
10
Required minimum illuminance Minimum illuminance Maximum illuminance Uniformity Height Calculation algorithm used Maintenance factor
4
6
8
10
20
12
30
14
[m] 1 : 100 40
: 1 lx Emin Emax Emin/Emax
: 1.1 lx : 20 lx : 1 : 18.40 (0.05) (Threshold value 1:40) :0m : Direct component : 0.8
Produced by Ansell Lighting Design Department Moxy Stratford plot Revision D 170824
Page 20/71
Object Installation Project number Date
1.3
: : : :
Moxy Stratford Revision D New Proposed Lighting 99-29873-MR 24.08.2017
Calculation results, GROUND FLOOR
1.3.6 Boundary line, CIRCULATION (E)
[m] 8
7
6
5
4
3
2
1
0 0.0
Illuminance [lx]
1
1.0
10
Required minimum illuminance Minimum illuminance Maximum illuminance Uniformity Height Calculation algorithm used Maintenance factor
0.5
1.5
2.0
2.5
3.0
3.5
4.0
20
4.5
30
5.0
[m] 1 : 50 40
: 1 lx Emin Emax Emin/Emax
: 2 lx : 4.6 lx : 1 : 2.29 (0.44) (Threshold value 1:40) :0m : Direct component : 0.8
Produced by Ansell Lighting Design Department Moxy Stratford plot Revision D 170824
Page 21/71
Object Installation Project number Date
1.3
: : : :
Moxy Stratford Revision D New Proposed Lighting 99-29873-MR 24.08.2017
Calculation results, GROUND FLOOR
1.3.7 Boundary line, STAIR / LIFT LOBBY (E)
[m] 5.0
4.5
4.0
3.5
3.0
2.5
2.0
1.5
1.0
0.5
0.0 0.0 0.2 0.4 0.6 0.8 1.0 1.2 1.4 1.6
[m] 1 : 25
Illuminance [lx]
1
10
Required minimum illuminance Minimum illuminance Maximum illuminance Uniformity Height Calculation algorithm used Maintenance factor
20
30
40
: 1 lx Emin Emax Emin/Emax
: 1.1 lx : 3.1 lx : 1 : 2.80 (0.36) (Threshold value 1:40) :0m : Direct component : 0.8
Produced by Ansell Lighting Design Department Moxy Stratford plot Revision D 170824
Page 22/71
Object Installation Project number Date
1.3
: : : :
Moxy Stratford Revision D New Proposed Lighting 99-29873-MR 24.08.2017
Calculation results, GROUND FLOOR
1.3.8 Boundary line, CIRCULATION (E)
[m] 6
5
4
3
2
1
0 0.00
Illuminance [lx]
1
10
Required minimum illuminance Minimum illuminance Maximum illuminance Uniformity Height Calculation algorithm used Maintenance factor
[m] 1 : 50
20
30
40
: 1 lx Emin Emax Emin/Emax
: 4.1 lx : 5.6 lx : 1 : 1.38 (0.72) (Threshold value 1:40) :0m : Direct component : 0.8
Produced by Ansell Lighting Design Department Moxy Stratford plot Revision D 170824
Page 23/71
Object Installation Project number Date
1.3
: : : :
Moxy Stratford Revision D New Proposed Lighting 99-29873-MR 24.08.2017
Calculation results, GROUND FLOOR
1.3.9 Boundary line, FEMALE WC (E)
[m] 1.8 1.6 1.4 1.2 1.0 0.8 0.6 0.4 0.2 0.0 0.0
Illuminance [lx]
0.2
0.5
0.6
5
Required minimum illuminance Minimum illuminance Maximum illuminance Uniformity Height Calculation algorithm used Maintenance factor
0.4
0.8
1.0
1.2
1.4
1.6
1.8
10
2.0
15
2.2
2.4
[m] 1 : 20 20
: 0.5 lx Emin Emax Emin/Emax
: 2.2 lx : 3.1 lx : 1 : 1.43 (0.70) (Threshold value 1:40) :0m : Direct component : 0.8
Produced by Ansell Lighting Design Department Moxy Stratford plot Revision D 170824
Page 24/71
Object Installation Project number Date
1.3
: : : :
Moxy Stratford Revision D New Proposed Lighting 99-29873-MR 24.08.2017
Calculation results, GROUND FLOOR
1.3.10 Boundary line, WC LOBBY (E)
[m] 0.8 0.7 0.6 0.5 0.4 0.3 0.2 0.1 0.0 0.0
Illuminance [lx]
0.2
1
10
Required minimum illuminance Minimum illuminance Maximum illuminance Uniformity Height Calculation algorithm used Maintenance factor
0.4
0.6
0.8
1.0
1.2
1.4
1.6
20
1.8
2.0
30
2.2
2.4
[m] 1 : 20 40
: 1 lx Emin Emax Emin/Emax
: 2.2 lx : 3.1 lx : 1 : 1.41 (0.71) (Threshold value 1:40) :0m : Direct component : 0.8
Produced by Ansell Lighting Design Department Moxy Stratford plot Revision D 170824
Page 25/71
Object Installation Project number Date
1.3
: : : :
Moxy Stratford Revision D New Proposed Lighting 99-29873-MR 24.08.2017
Calculation results, GROUND FLOOR
1.3.11 Boundary line, WC LOBBY (E)
[m] 2.0 1.8 1.6 1.4 1.2 1.0 0.8 0.6 0.4 0.2 0.0 0.0
Illuminance [lx]
0.5
0.5
5
Required minimum illuminance Minimum illuminance Maximum illuminance Uniformity Height Calculation algorithm used Maintenance factor
1.0
1.5
2.0
2.5
10
3.0
15
3.5
[m] 1 : 25 20
: 0.5 lx Emin Emax Emin/Emax
: 1.6 lx : 3.1 lx : 1 : 1.92 (0.52) (Threshold value 1:40) :0m : Direct component : 0.8
Produced by Ansell Lighting Design Department Moxy Stratford plot Revision D 170824
Page 26/71
Object Installation Project number Date
1.3
: : : :
Moxy Stratford Revision D New Proposed Lighting 99-29873-MR 24.08.2017
Calculation results, GROUND FLOOR
1.3.12 Boundary line, LOBBY (E)
[m] 1.0 0.9 0.8 0.7 0.6 0.5 0.4 0.3 0.2 0.1 0.0 0.0
Illuminance [lx]
0.2
0.4
1
10
Required minimum illuminance Minimum illuminance Maximum illuminance Uniformity Height Calculation algorithm used Maintenance factor
0.6
0.8
1.0
20
1.2
1.4
30
1.6
[m] 1 : 10 40
: 1 lx Emin Emax Emin/Emax
: 2.1 lx : 2.4 lx : 1 : 1.13 (0.88) (Threshold value 1:40) :0m : Direct component : 0.8
Produced by Ansell Lighting Design Department Moxy Stratford plot Revision D 170824
Page 27/71
Object Installation Project number Date
1.3
: : : :
Moxy Stratford Revision D New Proposed Lighting 99-29873-MR 24.08.2017
Calculation results, GROUND FLOOR
1.3.13 Boundary line, LOBBY (E)
[m] 0.9
0.8
0.7
0.6
0.5
0.4
0.3
0.2
0.1
0.0 0.00 0.05 0.10 0.15 0.20 0.25 0.30 0.35 0.40 0.45 0.50 0.55
Illuminance [lx]
1
10
Required minimum illuminance Minimum illuminance Maximum illuminance Uniformity Height Calculation algorithm used Maintenance factor
20
30
[m] 1:5 40
: 1 lx Emin Emax Emin/Emax
: 1.1 lx : 1.2 lx : 1 : 1.11 (0.90) (Threshold value 1:40) :0m : Direct component : 0.8
Produced by Ansell Lighting Design Department Moxy Stratford plot Revision D 170824
Page 28/71
Object Installation Project number Date
1.3
: : : :
Moxy Stratford Revision D New Proposed Lighting 99-29873-MR 24.08.2017
Calculation results, GROUND FLOOR
1.3.14 Boundary line, MALE WC (E)
[m] 1.8 1.6 1.4 1.2 1.0 0.8 0.6 0.4 0.2 0.0 0.00 0.25 0.50 0.75 1.00 1.25 1.50 1.75 2.00 2.25 2.50
[m] 1 : 25
Illuminance [lx]
0.5
5
Required minimum illuminance Minimum illuminance Maximum illuminance Uniformity Height Calculation algorithm used Maintenance factor
10
15
20
: 0.5 lx Emin Emax Emin/Emax
: 1.9 lx : 3.1 lx : 1 : 1.62 (0.62) (Threshold value 1:40) :0m : Direct component : 0.8
Produced by Ansell Lighting Design Department Moxy Stratford plot Revision D 170824
Page 29/71
Object Installation Project number Date
1.3
: : : :
Moxy Stratford Revision D New Proposed Lighting 99-29873-MR 24.08.2017
Calculation results, GROUND FLOOR
1.3.15 Boundary line, ASSISTED WC (E)
[m] 1.2
1.0
0.8
0.6
0.4
0.2
0.0 0.0
Illuminance [lx]
0.5
5
Required minimum illuminance Minimum illuminance Maximum illuminance Uniformity Height Calculation algorithm used Maintenance factor
0.1
0.2
0.3
0.4
0.5
0.6
10
0.7
[m] 1 : 10 15
20
: 0.5 lx Emin Emax Emin/Emax
: 2.2 lx : 3 lx : 1 : 1.39 (0.72) (Threshold value 1:40) :0m : Direct component : 0.8
Produced by Ansell Lighting Design Department Moxy Stratford plot Revision D 170824
Page 30/71
Object Installation Project number Date
1.3
: : : :
Moxy Stratford Revision D New Proposed Lighting 99-29873-MR 24.08.2017
Calculation results, GROUND FLOOR
1.3.16 Boundary line, ASSISTED WC (E)
[m] 1.6
1.4
1.2
1.0
0.8
0.6
0.4
0.2
0.0 0.0
Illuminance [lx]
0.2
0.5
5
Required minimum illuminance Minimum illuminance Maximum illuminance Uniformity Height Calculation algorithm used Maintenance factor
0.4
0.6
0.8
10
1.0
1.2
15
1.4
[m] 1 : 10 20
: 0.5 lx Emin Emax Emin/Emax
: 2.3 lx : 3.1 lx : 1 : 1.33 (0.75) (Threshold value 1:40) :0m : Direct component : 0.8
Produced by Ansell Lighting Design Department Moxy Stratford plot Revision D 170824
Page 31/71
Object Installation Project number Date
1.3
: : : :
Moxy Stratford Revision D New Proposed Lighting 99-29873-MR 24.08.2017
Calculation results, GROUND FLOOR
1.3.17 Boundary line, FOYER / BAR / SEATING AREA.1 (E)
[m] 20 18 16 14 12 10 8 6 4 2 0 0
Illuminance [lx]
5
10
0.5
5
Required minimum illuminance Minimum illuminance Maximum illuminance Uniformity Height Calculation algorithm used Maintenance factor
15
20
25
10
30
35
15
40
[m] 1 : 250 20
: 0.5 lx Emin Emax Emin/Emax
: 0.5 lx : 4.4 lx : 1 : 8.92 (0.11) (Threshold value 1:40) :0m : Direct component : 0.8
Produced by Ansell Lighting Design Department Moxy Stratford plot Revision D 170824
Page 32/71
Object Installation Project number Date
1.3
: : : :
Moxy Stratford Revision D New Proposed Lighting 99-29873-MR 24.08.2017
Calculation results, GROUND FLOOR
1.3.18 Boundary line, KITCHEN (E)
[m] 14 12 10 8 6 4 2 0 0
Illuminance [lx]
2
0.5
6
5
Required minimum illuminance Minimum illuminance Maximum illuminance Uniformity Height Calculation algorithm used Maintenance factor
4
8
10
12
14
16
10
18
20
15
22
[m] 1 : 200 20
: 0.5 lx Emin Emax Emin/Emax
: 1 lx : 6 lx : 1 : 5.79 (0.17) (Threshold value 1:40) : 0.9 m : Direct component : 0.8
Produced by Ansell Lighting Design Department Moxy Stratford plot Revision D 170824
Page 33/71
Object Installation Project number Date
1.3
: : : :
Moxy Stratford Revision D New Proposed Lighting 99-29873-MR 24.08.2017
Calculation results, GROUND FLOOR
1.3.19 Boundary line, STORE (E)
[m] 9
8
7
6
5
4
3
2
1
0 0
Illuminance [lx]
1
0.5
5
Required minimum illuminance Minimum illuminance Maximum illuminance Uniformity Height Calculation algorithm used Maintenance factor
2
3
4
10
5
6
15
7
[m] 1 : 50 20
: 0.5 lx Emin Emax Emin/Emax
: 0.8 lx : 3.8 lx : 1 : 4.90 (0.20) (Threshold value 1:40) :0m : Direct component : 0.8
Produced by Ansell Lighting Design Department Moxy Stratford plot Revision D 170824
Page 34/71
Object Installation Project number Date
1.3
: : : :
Moxy Stratford Revision D New Proposed Lighting 99-29873-MR 24.08.2017
Calculation results, GROUND FLOOR
1.3.20 Boundary line, PLANT ROOM (E)
[m] 18
16
14
12
10
8
6
4
2
0 0
Illuminance [lx]
2
15
150
Required minimum illuminance Minimum illuminance Maximum illuminance Uniformity Height Calculation algorithm used Maintenance factor
4
6
8
10
300
12
450
14
[m] 1 : 100 600
: 15 lx Emin Emax Emin/Emax
: 14 lx : 35 lx : 1 : 2.52 (0.40) (Threshold value 1:40) :0m : Direct component : 0.8
Produced by Ansell Lighting Design Department Moxy Stratford plot Revision D 170824
Page 35/71
Object Installation Project number Date
1.3
: : : :
Moxy Stratford Revision D New Proposed Lighting 99-29873-MR 24.08.2017
Summary, GROUND FLOOR
1.3.21 Result overview (emergency lighting) Type No.\Make ANSELL Order No. Luminaire name Equipment
: ASLED5/M3 : Industrial - Stormloc IP65 LED Non-Corrosive : 1 x 36.6 W / 3800 lm (6.4 %)
3
Order No. Luminaire name Equipment
: ARALED/OA/3NM/ST : Display - Raven LED Emergency Downlight : 1 x 3 W / 223.6 lm (100.0 %)
10
2
Order No. Luminaire name Equipment
: AFALED/ER/3NM/ST : Emergency - Falcon LED Surface Emergency Downlight : 1 x 5 W / 129.3 lm (100.0 %)
11
48
Order No. Luminaire name Equipment
: AFALED/OA/3NM/ST : Emergency - Falcon LED Surface Emergency Downlight : 1 x 5 W / 152.2 lm (100.0 %)
12
38
Order No. Luminaire name Equipment
: !ACELED/3M/ST : Emergency - Centurion LED Bulkhead : 1 x 6 W / 193 lm (100.0 %)
4
38
9
Result evaluation area Calculation algorithm used: Direct component Maintenance factor: 0.8 Reference planes for emergency lighting: Surface No. Default[lx] Emin[lx] Emax[lx] Uniformity Height LOADING BAY / DISABLED PARKING 24 0.5 0.5 7.8 1: 16.28 0.00 STAIRS 2
1.0
1.0
2.0
1: 1.89
0.00
STAIRS 6
1.0
2.0
5.0
1: 2.51
0.00
STAIRS 9
1.0
1.0
3.0
1: 2.83
0.00
CIRCULATION 4 1.0
1.1
19.5
1: 18.43
0.00
CIRCULATION 11 1.0
2.0
4.6
1: 2.29
0.00
STAIR / LIFT LOBBY 13 1.0
1.1
3.1
1: 2.80
0.00
CIRCULATION 16 1.0
4.1
5.6
1: 1.38
0.00
FEMALE WC 7 0.5
2.2
3.1
1: 1.43
0.00
WC LOBBY 8 1.0
2.2
3.1
1: 1.41
0.00
WC LOBBY 18 0.5
1.6
3.1
1: 1.92
0.00
LOBBY 10
2.1
2.4
1: 1.13
0.00
1.0
Produced by Ansell Lighting Design Department Moxy Stratford plot Revision D 170824
Page 36/71
Object Installation Project number Date
1.3
: : : :
Moxy Stratford Revision D New Proposed Lighting 99-29873-MR 24.08.2017
Summary, GROUND FLOOR
1.3.21 Result overview (emergency lighting) LOBBY 14
1.0
1.1
1.2
1: 1.11
0.00
MALE WC 12
0.5
1.9
3.1
1: 1.62
0.00
ASSISTED WC 15 0.5
2.2
3.0
1: 1.39
0.00
ASSISTED WC 17 0.5
2.3
3.1
1: 1.33
0.00
FOYER / BAR / SEATING AREA 19 0.5 0.5
4.4
1: 8.92
0.00
KITCHEN 20
0.5
1.0
6.0
1: 5.79
0.90
STORE 22
0.5
0.8
3.8
1: 4.90
0.00
PLANT ROOM 25 15.0
13.8
34.8
1: 2.52
0.00
Produced by Ansell Lighting Design Department Moxy Stratford plot Revision D 170824
Page 37/71
Object Installation Project number Date
: : : :
Moxy Stratford Revision D New Proposed Lighting 99-29873-MR 24.08.2017
2
FLOOR 1
2.1
Description, FLOOR 1
2.1.1 Floor plan
N [m] 20
15
10
5
0
-5
-10
-15
0
Wall x 1 34.04 m 2 37.39 m 3 37.08 m 4 39.89 m 5 51.94 m 6 0.01 m 7 0.00 m Floor Ceiling Room height Height of reference plane
5
y -17.13 m -10.63 m -10.46 m -4.86 m 22.55 m 22.53 m 0.00 m
10
Length 38.11 m 7.32 m 0.35 m 6.27 m 29.94 m 51.94 m 22.53 m
15
20
25
30
35
40
45
50 [m] 1 : 250
Reflectance 50.0 % 50.0 % 50.0 % 50.0 % 50.0 % 50.0 % 50.0 % 20.0 % 70.0 %
2.50 m ----
Produced by Ansell Lighting Design Department Moxy Stratford plot Revision D 170824
Page 39/71
Object Installation Project number Date
: : : :
Moxy Stratford Revision D New Proposed Lighting 99-29873-MR 24.08.2017
2
FLOOR 1
2.2
Summary, FLOOR 1
2.2.1 Result overview, LOBBY
N [m] 20
15
10
5
0
-5
-10
-15 0
Illuminance [lx]
5
100
10
15
20
25
150
30
200
General Calculation algorithm used Height of evaluation surface Maintenance factor
Average indirect fraction 0.00 m 0.80
Total luminous flux of all lamps Total power Total power per area (1420.40 m²)
15352.2002 lm 151.4 W 0.11 W/m²
Illuminance Average illuminance Minimum illuminance Maximum illuminance Uniformity Uo Diversity Ud
Eav Emin Emax Emin/Em Emin/Emax
35
40
45
300
50
[m]
500
248 lx 122 lx 303 lx 1:2.04 (0.49) 1:2.49 (0.4)
Type No.\Make ANSELL Order No. Luminaire name Equipment
: ASLED5 : Industrial - Stormloc IP65 LED Non-Corrosive : 1 x 36.6 W / 3800 lm
2
Order No. Luminaire name Equipment
: ASLED5/M3 : Industrial - Stormloc IP65 LED Non-Corrosive : 1 x 36.6 W / 3800 lm
1
Order No. Luminaire name Equipment
: AFALED/OA/3NM/ST : Emergency - Falcon LED Surface Emergency Downlight : 1 x 5 W / 152.2 lm(0%)
3
2
4
11
Produced by Ansell Lighting Design Department Moxy Stratford plot Revision D 170824
Page 40/71
Object Installation Project number Date
: : : :
Moxy Stratford Revision D New Proposed Lighting 99-29873-MR 24.08.2017
2
FLOOR 1
2.3
Calculation results, FLOOR 1
2.3.1 Boundary line, CIRCULATION (E)
[m] 0.50 0.00 0
Illuminance [lx]
2
4
1
10
Required minimum illuminance Minimum illuminance Maximum illuminance Uniformity Height Calculation algorithm used Maintenance factor
6
8
10
12
20
14
30
16
18
[m] 1 : 100 40
: 1 lx Emin Emax Emin/Emax
: 3 lx : 8.6 lx : 1 : 2.84 (0.35) (Threshold value 1:40) :0m : Direct component : 0.8
Produced by Ansell Lighting Design Department Moxy Stratford plot Revision D 170824
Page 41/71
Object Installation Project number Date
2.3
: : : :
Moxy Stratford Revision D New Proposed Lighting 99-29873-MR 24.08.2017
Calculation results, FLOOR 1
2.3.2 Boundary line, CIRCULATION (E)
[m] 24
22
20
18
16
14
12
10
8
6
4
2
0 0
Illuminance [lx]
2
4
6
1
10
Required minimum illuminance Minimum illuminance Maximum illuminance Uniformity Height Calculation algorithm used Maintenance factor
8
10
12
20
14
16
30
18
20
[m] 1 : 100 40
: 1 lx Emin Emax Emin/Emax
: 1.8 lx : 9.3 lx : 1 : 5.21 (0.19) (Threshold value 1:40) :0m : Direct component : 0.8
Produced by Ansell Lighting Design Department Moxy Stratford plot Revision D 170824
Page 42/71
Object Installation Project number Date
2.3
: : : :
Moxy Stratford Revision D New Proposed Lighting 99-29873-MR 24.08.2017
Calculation results, FLOOR 1
2.3.3 Boundary line, CIRCULATION (E)
[m] 0.50 0.00 0
Illuminance [lx]
2
4
1
8
10
Required minimum illuminance Minimum illuminance Maximum illuminance Uniformity Height Calculation algorithm used Maintenance factor
6
10
12
20
14
30
16
18
20
[m] 1 : 100 40
: 1 lx Emin Emax Emin/Emax
: 2.1 lx : 8.5 lx : 1 : 4.16 (0.24) (Threshold value 1:40) :0m : Direct component : 0.8
Produced by Ansell Lighting Design Department Moxy Stratford plot Revision D 170824
Page 43/71
Object Installation Project number Date
2.3
: : : :
Moxy Stratford Revision D New Proposed Lighting 99-29873-MR 24.08.2017
Calculation results, FLOOR 1
2.3.4 Boundary line, STAIRS (E)
[m] 4.5
4.0
3.5
3.0
2.5
2.0
1.5
1.0
0.5
0.0 0.0 0.2 0.4 0.6 0.8 1.0 1.2 1.4 1.6
[m] 1 : 25
Illuminance [lx]
1
10
Required minimum illuminance Minimum illuminance Maximum illuminance Uniformity Height Calculation algorithm used Maintenance factor
20
30
40
: 1 lx Emin Emax Emin/Emax
: 3.3 lx : 6.2 lx : 1 : 1.90 (0.53) (Threshold value 1:40) :0m : Direct component : 0.8
Produced by Ansell Lighting Design Department Moxy Stratford plot Revision D 170824
Page 44/71
Object Installation Project number Date
2.3
: : : :
Moxy Stratford Revision D New Proposed Lighting 99-29873-MR 24.08.2017
Calculation results, FLOOR 1
2.3.5 Boundary line, STAIRS (E)
[m] 4.5
4.0
3.5
3.0
2.5
2.0
1.5
1.0
0.5
0.0 0.0 0.2 0.4 0.6 0.8 1.0 1.2 1.4 1.6
[m] 1 : 25
Illuminance [lx]
1
10
Required minimum illuminance Minimum illuminance Maximum illuminance Uniformity Height Calculation algorithm used Maintenance factor
20
30
40
: 1 lx Emin Emax Emin/Emax
: 3.3 lx : 6 lx : 1 : 1.83 (0.55) (Threshold value 1:40) :0m : Direct component : 0.8
Produced by Ansell Lighting Design Department Moxy Stratford plot Revision D 170824
Page 45/71
Object Installation Project number Date
2.3
: : : :
Moxy Stratford Revision D New Proposed Lighting 99-29873-MR 24.08.2017
Calculation results, FLOOR 1
2.3.6 Boundary line, STAIRS (E)
[m] 4.0
3.5
3.0
2.5
2.0
1.5
1.0
0.5
0.0 0.0 0.2 0.4 0.6 0.8 1.0 1.2 1.4 1.6 1.8 2.0 2.2
[m] 1 : 25
Illuminance [lx]
1
10
Required minimum illuminance Minimum illuminance Maximum illuminance Uniformity Height Calculation algorithm used Maintenance factor
20
30
40
: 1 lx Emin Emax Emin/Emax
: 3.2 lx : 6.1 lx : 1 : 1.89 (0.53) (Threshold value 1:40) :0m : Direct component : 0.8
Produced by Ansell Lighting Design Department Moxy Stratford plot Revision D 170824
Page 46/71
Object Installation Project number Date
2.3
: : : :
Moxy Stratford Revision D New Proposed Lighting 99-29873-MR 24.08.2017
Calculation results, FLOOR 1
2.3.7 Boundary line, LOBBY (E)
[m] 4.5
4.0
3.5
3.0
2.5
2.0
1.5
1.0
0.5
0.0 0.0
Illuminance [lx]
0.5
1
10
Required minimum illuminance Minimum illuminance Maximum illuminance Uniformity Height Calculation algorithm used Maintenance factor
1.0
1.5
2.0
2.5
20
3.0
30
3.5
4.0
[m] 1 : 25 40
: 1 lx Emin Emax Emin/Emax
: 1.7 lx : 10 lx : 1 : 5.99 (0.17) (Threshold value 1:40) :0m : Direct component : 0.8
Produced by Ansell Lighting Design Department Moxy Stratford plot Revision D 170824
Page 47/71
Object Installation Project number Date
2.3
: : : :
Moxy Stratford Revision D New Proposed Lighting 99-29873-MR 24.08.2017
Calculation results, FLOOR 1
2.3.8 Boundary line, STAIR/LIFT LOBBY (E)
[m] 5.0
4.5
4.0
3.5
3.0
2.5
2.0
1.5
1.0
0.5
0.0 0.0 0.2 0.4 0.6 0.8 1.0 1.2 1.4 1.6 1.8 2.0 2.2
[m] 1 : 25
Illuminance [lx]
1
10
Required minimum illuminance Minimum illuminance Maximum illuminance Uniformity Height Calculation algorithm used Maintenance factor
20
30
40
: 1 lx Emin Emax Emin/Emax
: 1.2 lx : 6 lx : 1 : 5.14 (0.19) (Threshold value 1:40) :0m : Direct component : 0.8
Produced by Ansell Lighting Design Department Moxy Stratford plot Revision D 170824
Page 48/71
Object Installation Project number Date
2.3
: : : :
Moxy Stratford Revision D New Proposed Lighting 99-29873-MR 24.08.2017
Summary, FLOOR 1
2.3.9 Result overview (emergency lighting) Type No.\Make ANSELL Order No. Luminaire name Equipment
: ASLED5/M3 : Industrial - Stormloc IP65 LED Non-Corrosive : 1 x 36.6 W / 3800 lm (6.4 %)
10
Order No. Luminaire name Equipment
: ARALED/ER/3NM/ST : Display - Raven LED Emergency Downlight : 1 x 3 W / 175.5 lm (100.0 %)
7
Order No. Luminaire name Equipment
: AFALED/OA/3NM/ST : Emergency - Falcon LED Surface Emergency Downlight : 1 x 5 W / 152.2 lm (100.0 %)
4
2
8
11
Result evaluation area Calculation algorithm used: Direct component Maintenance factor: 0.8 Reference planes for emergency lighting: Surface No. Default[lx] Emin[lx] Emax[lx] CIRCULATION 3 1.0 3.0 8.6
Uniformity Height 1: 2.84
0.00
CIRCULATION 4 1.0
1.8
9.3
1: 5.21
0.00
CIRCULATION 5 1.0
2.1
8.5
1: 4.16
0.00
STAIRS 1
1.0
3.3
6.2
1: 1.90
0.00
STAIRS 6
1.0
3.3
6.0
1: 1.83
0.00
STAIRS 7
1.0
3.2
6.1
1: 1.89
0.00
LOBBY 1
1.0
1.7
10.0
1: 5.99
0.00
1.2
6.0
1: 5.14
0.00
STAIR/LIFT LOBBY 1 1.0
Produced by Ansell Lighting Design Department Moxy Stratford plot Revision D 170824
Page 49/71
Object Installation Project number Date
: : : :
Moxy Stratford Revision D New Proposed Lighting 99-29873-MR 24.08.2017
3
FLOOR 2
3.1
Description, FLOOR 2
3.1.1 Floor plan
N [m] 20
15
10
5
0
-5
-10
-15
0
Wall x 1 34.04 m 2 37.39 m 3 37.08 m 4 39.89 m 5 51.94 m 6 0.01 m 7 0.00 m Floor Ceiling Room height Height of reference plane
5
y -17.13 m -10.63 m -10.46 m -4.86 m 22.55 m 22.53 m 0.00 m
10
Length 38.11 m 7.32 m 0.35 m 6.27 m 29.94 m 51.94 m 22.53 m
15
20
25
30
35
40
45
50 [m] 1 : 250
Reflectance 50.0 % 50.0 % 50.0 % 50.0 % 50.0 % 50.0 % 50.0 % 20.0 % 70.0 %
2.50 m ----
Produced by Ansell Lighting Design Department Moxy Stratford plot Revision D 170824
Page 51/71
Object Installation Project number Date
: : : :
Moxy Stratford Revision D New Proposed Lighting 99-29873-MR 24.08.2017
4
FLOOR 3
4.1
Description, FLOOR 3
4.1.1 Floor plan
N [m] 20
15
10
5
0
-5
-10
-15
0
Wall x 1 34.04 m 2 37.39 m 3 37.08 m 4 39.89 m 5 51.94 m 6 0.01 m 7 0.00 m Floor Ceiling Room height Height of reference plane
5
y -17.13 m -10.63 m -10.46 m -4.86 m 22.55 m 22.53 m 0.00 m
10
Length 38.11 m 7.32 m 0.35 m 6.27 m 29.94 m 51.94 m 22.53 m
15
20
25
30
35
40
45
50 [m] 1 : 250
Reflectance 50.0 % 50.0 % 50.0 % 50.0 % 50.0 % 50.0 % 50.0 % 20.0 % 70.0 %
2.50 m ----
Produced by Ansell Lighting Design Department Moxy Stratford plot Revision D 170824
Page 52/71
Object Installation Project number Date
: : : :
Moxy Stratford Revision D New Proposed Lighting 99-29873-MR 24.08.2017
5
FLOOR 4
5.1
Description, FLOOR 4
5.1.1 Floor plan
N [m] 20
15
10
5
0
-5
-10
-15
0
Wall x 1 34.04 m 2 37.39 m 3 37.08 m 4 39.89 m 5 51.94 m 6 0.01 m 7 0.00 m Floor Ceiling Room height Height of reference plane
5
y -17.13 m -10.63 m -10.46 m -4.86 m 22.55 m 22.53 m 0.00 m
10
Length 38.11 m 7.32 m 0.35 m 6.27 m 29.94 m 51.94 m 22.53 m
15
20
25
30
35
40
45
50 [m] 1 : 250
Reflectance 50.0 % 50.0 % 50.0 % 50.0 % 50.0 % 50.0 % 50.0 % 20.0 % 70.0 %
2.50 m ----
Produced by Ansell Lighting Design Department Moxy Stratford plot Revision D 170824
Page 53/71
Object Installation Project number Date
: : : :
Moxy Stratford Revision D New Proposed Lighting 99-29873-MR 24.08.2017
6
FLOOR 5
6.1
Description, FLOOR 5
6.1.1 Floor plan
N [m] 20
15
10
5
0
-5
-10
-15
0
Wall x 1 34.04 m 2 37.39 m 3 37.08 m 4 39.89 m 5 51.94 m 6 0.01 m 7 0.00 m Floor Ceiling Room height Height of reference plane
5
y -17.13 m -10.63 m -10.46 m -4.86 m 22.55 m 22.53 m 0.00 m
10
Length 38.11 m 7.32 m 0.35 m 6.27 m 29.94 m 51.94 m 22.53 m
15
20
25
30
35
40
45
50 [m] 1 : 250
Reflectance 50.0 % 50.0 % 50.0 % 50.0 % 50.0 % 50.0 % 50.0 % 20.0 % 70.0 %
2.50 m ----
Produced by Ansell Lighting Design Department Moxy Stratford plot Revision D 170824
Page 54/71
Object Installation Project number Date
: : : :
Moxy Stratford Revision D New Proposed Lighting 99-29873-MR 24.08.2017
7
FLOOR 6
7.1
Description, FLOOR 6
7.1.1 Floor plan
N [m] 20
15
10
5
0
-5
-10
-15
0
Wall x 1 34.04 m 2 37.39 m 3 37.08 m 4 39.89 m 5 51.94 m 6 0.01 m 7 0.00 m Floor Ceiling Room height Height of reference plane
5
y -17.13 m -10.63 m -10.46 m -4.86 m 22.55 m 22.53 m 0.00 m
10
Length 38.11 m 7.32 m 0.35 m 6.27 m 29.94 m 51.94 m 22.53 m
15
20
25
30
35
40
45
50 [m] 1 : 250
Reflectance 50.0 % 50.0 % 50.0 % 50.0 % 50.0 % 50.0 % 50.0 % 20.0 % 70.0 %
2.50 m ----
Produced by Ansell Lighting Design Department Moxy Stratford plot Revision D 170824
Page 55/71
Object Installation Project number Date
: : : :
Moxy Stratford Revision D New Proposed Lighting 99-29873-MR 24.08.2017
8
FLOOR 7
8.1
Description, FLOOR 7
8.1.1 Floor plan
N [m] 20
15
10
5
0
-5
-10
-15
0
Wall x 1 34.04 m 2 37.39 m 3 37.08 m 4 39.89 m 5 51.94 m 6 0.01 m 7 0.00 m Floor Ceiling Room height Height of reference plane
5
y -17.13 m -10.63 m -10.46 m -4.86 m 22.55 m 22.53 m 0.00 m
10
Length 38.11 m 7.32 m 0.35 m 6.27 m 29.94 m 51.94 m 22.53 m
15
20
25
30
35
40
45
50 [m] 1 : 250
Reflectance 50.0 % 50.0 % 50.0 % 50.0 % 50.0 % 50.0 % 50.0 % 20.0 % 70.0 %
2.50 m ----
Produced by Ansell Lighting Design Department Moxy Stratford plot Revision D 170824
Page 56/71
Object Installation Project number Date
: : : :
Moxy Stratford Revision D New Proposed Lighting 99-29873-MR 24.08.2017
8
FLOOR 7
8.2
Summary, FLOOR 7
8.2.1 Result overview, LOBBY
N [m] 20
15
10
5
0
-5
-10
-15 0
Illuminance [lx]
5
100
10
15
20
25
150
30
200
General Calculation algorithm used Height of evaluation surface Maintenance factor
Average indirect fraction 0.00 m 0.80
Total luminous flux of all lamps Total power Total power per area (1420.40 m²)
15200 lm 146.4 W 0.10 W/m²
Illuminance Average illuminance Minimum illuminance Maximum illuminance Uniformity Uo Diversity Ud
Eav Emin Emax Emin/Em Emin/Emax
35
40
45
300
50
[m]
500
248 lx 121 lx 303 lx 1:2.04 (0.49) 1:2.49 (0.4)
Type No.\Make
3
2
4
2
ANSELL Order No. Luminaire name Equipment
: ASLED5 : Industrial - Stormloc IP65 LED Non-Corrosive : 1 x 36.6 W / 3800 lm
Order No. Luminaire name Equipment
: ASLED5/M3 : Industrial - Stormloc IP65 LED Non-Corrosive : 1 x 36.6 W / 3800 lm
Produced by Ansell Lighting Design Department Moxy Stratford plot Revision D 170824
Page 57/71
Object Installation Project number Date
: : : :
Moxy Stratford Revision D New Proposed Lighting 99-29873-MR 24.08.2017
8
FLOOR 7
8.3
Calculation results, FLOOR 7
8.3.1 Boundary line, CIRCULATION (E)
[m] 0.50 0.00 0
Illuminance [lx]
2
4
1
10
Required minimum illuminance Minimum illuminance Maximum illuminance Uniformity Height Calculation algorithm used Maintenance factor
6
8
10
12
20
14
30
16
18
[m] 1 : 100 40
: 1 lx Emin Emax Emin/Emax
: 2.8 lx : 8.6 lx : 1 : 3.08 (0.32) (Threshold value 1:40) :0m : Direct component : 0.8
Produced by Ansell Lighting Design Department Moxy Stratford plot Revision D 170824
Page 58/71
Object Installation Project number Date
8.3
: : : :
Moxy Stratford Revision D New Proposed Lighting 99-29873-MR 24.08.2017
Calculation results, FLOOR 7
8.3.2 Boundary line, CIRCULATION (E)
[m] 24
22
20
18
16
14
12
10
8
6
4
2
0 0
Illuminance [lx]
2
4
6
1
10
Required minimum illuminance Minimum illuminance Maximum illuminance Uniformity Height Calculation algorithm used Maintenance factor
8
10
12
20
14
16
30
18
20
[m] 1 : 100 40
: 1 lx Emin Emax Emin/Emax
: 1.8 lx : 9.2 lx : 1 : 5.17 (0.19) (Threshold value 1:40) :0m : Direct component : 0.8
Produced by Ansell Lighting Design Department Moxy Stratford plot Revision D 170824
Page 59/71
Object Installation Project number Date
8.3
: : : :
Moxy Stratford Revision D New Proposed Lighting 99-29873-MR 24.08.2017
Calculation results, FLOOR 7
8.3.3 Boundary line, CIRCULATION (E)
[m] 0.50 0.00 0
Illuminance [lx]
2
4
1
8
10
Required minimum illuminance Minimum illuminance Maximum illuminance Uniformity Height Calculation algorithm used Maintenance factor
6
10
12
20
14
30
16
18
20
[m] 1 : 100 40
: 1 lx Emin Emax Emin/Emax
: 2.1 lx : 8.5 lx : 1 : 4.16 (0.24) (Threshold value 1:40) :0m : Direct component : 0.8
Produced by Ansell Lighting Design Department Moxy Stratford plot Revision D 170824
Page 60/71
Object Installation Project number Date
8.3
: : : :
Moxy Stratford Revision D New Proposed Lighting 99-29873-MR 24.08.2017
Calculation results, FLOOR 7
8.3.4 Boundary line, STAIRS (E)
[m] 4.5
4.0
3.5
3.0
2.5
2.0
1.5
1.0
0.5
0.0 0.0 0.2 0.4 0.6 0.8 1.0 1.2 1.4 1.6
[m] 1 : 25
Illuminance [lx]
1
10
Required minimum illuminance Minimum illuminance Maximum illuminance Uniformity Height Calculation algorithm used Maintenance factor
20
30
40
: 1 lx Emin Emax Emin/Emax
: 3.3 lx : 6.1 lx : 1 : 1.87 (0.53) (Threshold value 1:40) :0m : Direct component : 0.8
Produced by Ansell Lighting Design Department Moxy Stratford plot Revision D 170824
Page 61/71
Object Installation Project number Date
8.3
: : : :
Moxy Stratford Revision D New Proposed Lighting 99-29873-MR 24.08.2017
Calculation results, FLOOR 7
8.3.5 Boundary line, STAIRS (E)
[m] 4.5
4.0
3.5
3.0
2.5
2.0
1.5
1.0
0.5
0.0 0.0 0.2 0.4 0.6 0.8 1.0 1.2 1.4 1.6
[m] 1 : 25
Illuminance [lx]
1
10
Required minimum illuminance Minimum illuminance Maximum illuminance Uniformity Height Calculation algorithm used Maintenance factor
20
30
40
: 1 lx Emin Emax Emin/Emax
: 3.3 lx : 6 lx : 1 : 1.83 (0.55) (Threshold value 1:40) :0m : Direct component : 0.8
Produced by Ansell Lighting Design Department Moxy Stratford plot Revision D 170824
Page 62/71
Object Installation Project number Date
8.3
: : : :
Moxy Stratford Revision D New Proposed Lighting 99-29873-MR 24.08.2017
Calculation results, FLOOR 7
8.3.6 Boundary line, STAIRS (E)
[m] 4.0
3.5
3.0
2.5
2.0
1.5
1.0
0.5
0.0 0.0 0.2 0.4 0.6 0.8 1.0 1.2 1.4 1.6 1.8 2.0 2.2
[m] 1 : 25
Illuminance [lx]
1
10
Required minimum illuminance Minimum illuminance Maximum illuminance Uniformity Height Calculation algorithm used Maintenance factor
20
30
40
: 1 lx Emin Emax Emin/Emax
: 3.3 lx : 6.1 lx : 1 : 1.88 (0.53) (Threshold value 1:40) :0m : Direct component : 0.8
Produced by Ansell Lighting Design Department Moxy Stratford plot Revision D 170824
Page 63/71
Object Installation Project number Date
8.3
: : : :
Moxy Stratford Revision D New Proposed Lighting 99-29873-MR 24.08.2017
Calculation results, FLOOR 7
8.3.7 Boundary line, LOBBY (E)
[m] 4.5
4.0
3.5
3.0
2.5
2.0
1.5
1.0
0.5
0.0 0.0
Illuminance [lx]
0.5
1
10
Required minimum illuminance Minimum illuminance Maximum illuminance Uniformity Height Calculation algorithm used Maintenance factor
1.0
1.5
2.0
2.5
20
3.0
30
3.5
4.0
[m] 1 : 25 40
: 1 lx Emin Emax Emin/Emax
: 1.7 lx : 10 lx : 1 : 5.99 (0.17) (Threshold value 1:40) :0m : Direct component : 0.8
Produced by Ansell Lighting Design Department Moxy Stratford plot Revision D 170824
Page 64/71
Object Installation Project number Date
8.3
: : : :
Moxy Stratford Revision D New Proposed Lighting 99-29873-MR 24.08.2017
Calculation results, FLOOR 7
8.3.8 Boundary line, STAIR/LIFT LOBBY (E)
[m] 5.0
4.5
4.0
3.5
3.0
2.5
2.0
1.5
1.0
0.5
0.0 0.0 0.2 0.4 0.6 0.8 1.0 1.2 1.4 1.6 1.8 2.0 2.2
[m] 1 : 25
Illuminance [lx]
1
10
Required minimum illuminance Minimum illuminance Maximum illuminance Uniformity Height Calculation algorithm used Maintenance factor
20
30
40
: 1 lx Emin Emax Emin/Emax
: 2.6 lx : 38 lx : 1 : 14.40 (0.07) (Threshold value 1:40) :0m : Direct component : 0.8
Produced by Ansell Lighting Design Department Moxy Stratford plot Revision D 170824
Page 65/71
Object Installation Project number Date
8.3
: : : :
Moxy Stratford Revision D New Proposed Lighting 99-29873-MR 24.08.2017
Summary, FLOOR 7
8.3.9 Result overview (emergency lighting) Type No.\Make
1
1
4
2
8
ANSELL - Emergency Order No. : !AENLED/3M/W/ST Luminaire name : ENCORE LED Exit Sign Equipment : 1 x / 124 lm (0.8 %) ANSELL Order No. Luminaire name Equipment
: ASLED5/M3 : Industrial - Stormloc IP65 LED Non-Corrosive : 1 x 36.6 W / 3800 lm (6.4 %)
10
Order No. Luminaire name Equipment
: ARALED/ER/3NM/ST : Display - Raven LED Emergency Downlight : 1 x 3 W / 175.5 lm (100.0 %)
9
2
Order No. Luminaire name Equipment
: ARALED/OA/3NM/ST : Display - Raven LED Emergency Downlight : 1 x 3 W / 223.6 lm (100.0 %)
11
6
Order No. Luminaire name Equipment
: AFALED/OA/3NM/ST : Emergency - Falcon LED Surface Emergency Downlight : 1 x 5 W / 152.2 lm (100.0 %)
Result evaluation area Calculation algorithm used: Direct component Maintenance factor: 0.8 Reference planes for emergency lighting: Surface No. Default[lx] Emin[lx] Emax[lx] CIRCULATION 3 1.0 2.8 8.6
Uniformity Height 1: 3.08
0.00
CIRCULATION 4 1.0
1.8
9.2
1: 5.17
0.00
CIRCULATION 5 1.0
2.1
8.5
1: 4.16
0.00
STAIRS 1
1.0
3.3
6.1
1: 1.87
0.00
STAIRS 6
1.0
3.3
6.0
1: 1.83
0.00
STAIRS 7
1.0
3.3
6.1
1: 1.88
0.00
LOBBY 1
1.0
1.7
10.0
1: 5.99
0.00
2.6
38.0
1: 14.38
0.00
STAIR/LIFT LOBBY 1 1.0
Produced by Ansell Lighting Design Department Moxy Stratford plot Revision D 170824
Page 66/71
Object Installation Project number Date
: : : :
Moxy Stratford Revision D New Proposed Lighting 99-29873-MR 24.08.2017
9
ROOFTOP
9.1
Description, ROOFTOP
9.1.1 Floor plan
[m] 25
N
20
15
10
5
0
-5
-10
-15
-20
0
5
10
15
20
25
30
35
40
[m] 1 : 250
Produced by Ansell Lighting Design Department Moxy Stratford plot Revision D 170824
Page 68/71
Object Installation Project number Date
: : : :
Moxy Stratford Revision D New Proposed Lighting 99-29873-MR 24.08.2017
9
ROOFTOP
9.2
Summary, ROOFTOP
9.2.1 Result overview, Rooftop
[m] 25
N
20
15
10
5
0
-5
-10
-15
-20
0
Illuminance [lx]
50
5
10
15
75
20
Average indirect fraction 0.00 m 0.80
Total luminous flux of all lamps Total power Total power per area (2288.68 m²)
326800 lm 3139 W 1.37 W/m²
Eav Emin Emax Emin/Em Emin/Emax
30
100
General Calculation algorithm used Height of evaluation surface Maintenance factor
Illuminance Average illuminance Minimum illuminance Maximum illuminance Uniformity Uo Diversity Ud
25
35
40
150
[m]
200
123 lx 60 lx 315 lx 1:2.05 (0.49) 1:5.26 (0.19)
Type No.\Make
5
14
6
29
ANSELL Order No. Luminaire name Equipment
: ASLED2X5 : Industrial - Stormloc IP65 LED Non-Corrosive : 1 x 73 W / 7600 lm
Order No. Luminaire name Equipment
: ASLED2X5/M3 : Industrial - Stormloc IP65 LED Non-Corrosive : 1 x 73 W / 7600 lm
Produced by Ansell Lighting Design Department Moxy Stratford plot Revision D 170824
Page 69/71
Object Installation Project number Date
: : : :
Moxy Stratford Revision D New Proposed Lighting 99-29873-MR 24.08.2017
9
ROOFTOP
9.3
Calculation results, ROOFTOP
9.3.1 Boundary line, Rooftop (Em) (E)
[m] 35
30
25
20
15
10
5
0 0
Illuminance [lx]
5
0.5
5
Required minimum illuminance Minimum illuminance Maximum illuminance Uniformity Height Calculation algorithm used Maintenance factor
10
15
20
10
25
30
[m] 1 : 250 15
20
: 0.5 lx Emin Emax Emin/Emax
: 0.4 lx : 9.4 lx : 1 : 25.90 (0.04) (Threshold value 1:40) :0m : Direct component : 0.8
Produced by Ansell Lighting Design Department Moxy Stratford plot Revision D 170824
Page 70/71
Object Installation Project number Date
9.3
: : : :
Moxy Stratford Revision D New Proposed Lighting 99-29873-MR 24.08.2017
Summary, ROOFTOP
9.3.2 Result overview (emergency lighting) Type No.\Make
6
29
ANSELL Order No. Luminaire name Equipment
: ASLED2X5/M3 : Industrial - Stormloc IP65 LED Non-Corrosive : 1 x 73 W / 7600 lm (3.2 %)
Result evaluation area Calculation algorithm used: Direct component Maintenance factor: 0.8 Reference planes for emergency lighting: Surface No. Default[lx] Emin[lx] Emax[lx] Uniformity Height Rooftop (Em) 2 0.5 0.4 9.4 1: 25.93 0.00
Produced by Ansell Lighting Design Department Moxy Stratford plot Revision D 170824
Page 71/71