A B C D E F G H I J K L M N O 9 10 11 12 1313a1414a 15 1617 19 2020a2121a Please refer to PA1064-M-601 for plantroom layout PLANT ROOM 014 LINEN ROOM ...
8 downloads
13 Views
2MB Size
Notes
Heating Pipework Insulation
9
10
11
12
1313a 14a 14
15
1617
20 20a 21a 21
19
A
Reference AC01 AC02 AC03 AC04 AC05 AC06 AC07 AC08 AC09 AC10 AC11 AC12 AC13 AC14 AC15
CORE 4
Pipework relocated within undercroft to suit holes within steelwork at client request
? MEETING 1 ? 045
046
FCU01 FCU02 FCU03 FCU04 FCU05 FCU06 FCU07 FCU08 FCU09 FCU10 FCU11 FCU12 FCU13 FCU14 FCU15 FCU16 FCU17 FCU18
MEETING 2 AC20
047
AC12 15Ø CT LTHW F&R 25Ø CHW F&R to serve AC/FCU 20Ø CT LTHW F&R 32Ø CHW F&R to serve AC/FCU
15Ø CT LTHW F&R 25Ø CHW F&R to serve AC/FCU 15Ø CT LTHW F&R 25Ø CHW F&R to serve AC/FCU
B
FCU09
FCU10
AP 25Ø CT LTHW F&R 40Ø CHW F&R to serve AC/FCU
C 25Ø CT LTHW F&R 40Ø CHW F&R to serve AC/FCU
D
CORRIDOR
E
010
FCU08 15Ø CT LTHW F&R 25Ø CHW F&R to serve AC/FCU
R09
TBC F
RISER 2 009
FCU07 15Ø CT LTHW F&R 25Ø CHW F&R to serve AC/FCU
012 R08
CORE 2 ?
AC05
25Ø CT LTHW F&R 50Ø CHW F&R to serve AC/FCU 15Ø CT LTHW F&R 25Ø CHW F&R to serve AC/FCU
? 013
G H
15Ø CT LTHW F&R 25Ø CHW F&R to serve AC/FCU
AC06
Bellows
32Ø CT LTHW F&R 50Ø CHW F&R to serve AC/FCU
15Ø CT LTHW F&R 25Ø CHW F&R to serve AC/FCU FCU06
32Ø CT LTHW F&R 50Ø CHW F&R to serve AC/FCU
65Ø CT LTHW F&R 100Ø CHW F&R to serve AC/FCU
AC07 Please refer to PA1064-M-601 for plantroom layout
FCU05
Manufacture Biddle Biddle Biddle Biddle Biddle Biddle Biddle Biddle Biddle Biddle Biddle Biddle Biddle Biddle Biddle
Model CC90-H1C2 CC90-H1C2 CC90-H1C2 CC90-H1C2 CC90-H1C2 CC90-H1C2 CC90-H1C2 CC90-H1C2 CC60-C2 CC60-C2 CC90-H1C2 TBC TBC TBC TBC
Biddle Biddle Biddle Biddle Biddle Biddle Biddle Biddle Biddle Biddle Biddle Biddle Biddle Biddle Biddle Biddle Biddle Biddle
PB5 PB5 PB5 PB5 PB5 PB5 PB5 PB5 PB5 PB5 PB5 PB5 PB5 PB5 PB5 PB5 PB5 PB5
Pipe Size NB (mm)
Thickness (mm) of Mineral Wool
1.
This drawing shall be read in conjunction with all other services, Architectural drawings, project specifications and contract documentation.
2.
LSV regulating valves should be used to regulate individual emitters. DRV and CSV should be used on all sub branches and main branches.
3.
AAV's to be installed where pipework deviates to a higher location.
4.
All manifold 3-Port control valves to be linked into BMS. Each zone to have set back to 10°C for frost protection.
5.
All pipework shall be Mild steel medium grade (conforming with BS 1387 / EN 10255) using screwed / welded joints & fittings.
6.
The contractor's commissioning specialist shall review all drawings prior to installation to ensure each system can be commissioned correctly.
7.
The chemical cleaning specialist shall review all the drawings prior to installation and advise the location of flushing points and air vents.
8.
Pipework should be installed to facilitate self venting, dynamic flushing and draining. Where is is unavoidable, the use of manual air vents and drain points shall be installed.
9.
Contractor to provide coordinated services drawings including site measurements prior to manufacture and any installation work.
10.
Underfloor heating sub-contractor is responsible for obtaining and coordinating all floor drainage, IPS and furniture layouts.
11.
The contractor will allow adequate provision for expansion within pipework with the use of anchors and guides.
LTHW 15
25
20
30
25
35
32
35
40
35
50
40
65
40
80
45
100
45
125
45
150
50
All insulation thickness should be taken to the closest pipe size.
Steel Pipework Support Distances Pipe Size NB Vertical Run Horizontal Run (m) (mm) (mm) 15 2.0 2 20
2.4
3
25
2.7
3
32
2.7
3
40
3.0
3.5
50
3.4
3.5
65 & above
3.7
4.5
Ref
Manufacture
Model
R08 R09 R10 R11 R12 R13 R14 R15 R17 R18 R19 R20
Dimplex Dimplex Dimplex Dimplex Dimplex Dimplex Dimplex Dimplex Dimplex Dimplex Dimplex Dimplex
QRAD QRAD QRAD QRAD QRAD QRAD QRAD QRAD QRAD QRAD QRAD QRAD
Width (mm) 513 513 513 756 513 513 513 756 756 756 918 513
Height (mm) 546 546 546 546 546 546 546 546 546 546 546 546
Depth (mm) 105 105 105 105 105 105 105 105 105 105 105 105
32Ø CT LTHW F&R 50Ø CHW F&R to serve AC/FCU
32Ø CT LTHW F&R 50Ø CHW F&R to serve AC/FCU
ACCESSIBLE TOILET ? 017 ?
Output (W) 750 500 500 1500 750 500 750 1500 1500 1500 2000 750
FCU
FCU02
IV
FCU03
Flushing Bypass
AP
STR
IV
R10
I
SMOKE VENT 021 FCU01 50Ø CT LTHW F&R 80Ø CHW F&R to serve AC/FCU
R11
?R13 BABY CHANGING R12
PLANT ROOM 014
R14
?019
?
K
027
AP
M
DATA ROOM ? 025 ?
? ?
Please refer to PA1064-M-601 for plantroom layout
AP R18
AIRLINE CREW LOUNGE ?
LINEN ROOM
026 ?
028
AC08
C4 C3
SS SS
04.10.17 08.05.17
Updated Inline with Clients Comments. Refrigerant Pipework Added to AC units.
C2
SS
02.05.17
Updated Inline with Clients Comments.
C1
FR
18.04.17
Construction issue.
project
Moxy Heathrow
R15
title R17 O 50Ø CT LTHW F&R 80Ø CHW F&R to serve AC/FCU
50Ø CT LTHW F&R 80Ø CHW F&R to serve AC/FCU
15Ø CT LTHW F&R 25Ø CHW F&R to serve AC/FCU
IV
Detail A: Typical 4 Pipe Fan Coil Unit Connection Detail (NTS)
N Please refer to PA1064-M-601 for plantroom layout
STR
Frese modular pro balancing and temperature control valve R19
Bellows
IV Flushing Bypass
? 024
020 L
Frese modular pro balancing and temperature control valve
LUGGAGE ROOM
SECONDARY ENTRANCE LOBBY ? CORE 3 023 STORAGE/ADDITIONAL ? 022 LUGGAGE ?
FEMALE TOILETS
018
J
40Ø ? CT LTHW F&R 65Ø CHW F&R ? AC/FCU to serve
MALE TOILETS
?
80Ø CT LTHW F&R to serve DHW P.H.E
AP
50Ø CT LTHW F&R 80Ø CHW F&R to serve AC/FCU
Refrigeration Pipework from external condensers located on roof to serve wall mounted AC units within Data Room.
scale
Proposed LTHW/CHW Layout Serving AC & FCU's Ground Floor Sheet 2 of 3 1:100 @ A1
drawing no. PA1064
M-105
date
18.04.2017
rev. C4