SPECIFICA CONNESSIONI IN SITO - ON SITE CONNECTION DETAILS 1. ELETTRICA - ELECTRICAL Tipo - Type: OPTIONAL Tensione - Voltage: 400V / 3~+N+PE / 50Hz Potenza - Power: 5,25 kW / 8 A Fusibili - Fuse rating: 3 x 10 A Cavo e sezione min. - Cable and min. section: Colori dei cavi - Cable colours: L1: Nero - Black L2: Grigio - Gray L3: Marrone - Brown N: Blu - Blue PE: Giallo/Verde - Yellow/Green 2. ACQUA FREDDA - COLD WATER Connessione - Connection: Portata max. - Max. flow rate: Pressione dinamica min. - Min. flow pressure: Pressione max. - Max. pressure: Temperatura max. - Max. temperature: Durezza max. - Max. hardness:
3/4" maschio-male - DN20 25 lt/min 100 kPa (1,0 bar g) 800 kPa (8,0 bar g)
n.a. / 7...8 pH
3. ACQUA CALDA - WARM WATER Connessione - Connection: Portata max. - Max. flow rate: Pressione dinamica min.-Min. flow pressure: Pressione max. - Max. pressure: Temperatura max. - Max. temperature: Durezza max. - Max. hardness:
3/4" maschio-male - DN20 25 lt/min 100 kPa (1,0 bar g) 800 kPa (8,0 bar g)
n.a. / 7...8 pH
4. SCARICO PRINCIPALE - MAIN DRAIN Connessione - Connection: Portata max. - Peak flow rate: Altezza max. - Max. height: Temperatura max. - Max. temperature:
100 lt/min 0,420 m
ALTRE SPECIFICHE - OTHERS DETAILS AMBIENTE - ENVIRONMENT < 70 dB (A)
PESI - WEIGHTS Netto totale - Total Net: Lordo totale - Total Gross: Max all'uso - Max. on working: Carico a pavimento - Floor load:
CONFIGURAZIONE - CONFIGURATION A) Risc. in circolazione-Circulating heating type: X: N.A. B) Risc. in asciugatura-Air drying heating type: X: N.A. C) Risc. in taniche-Tanks water heating type: E: ELETTRICO-ELECTRICAL
NOTE - NOTES - La macchina deve essere livellata orizzontalmente. - L'alimentazione elettrica di ogni macchina deve essere protetta con un interruttore differenziale (30 mA, tipo "AC"). - Sono richiesti dei rubinetti/valvole manuali adiacenti alle connessioni per tutti i fluidi. - Per tutti gli scarichi canalizzati si deve prevenire il riflusso di condensa nella macchina. Posizionare i condotti di sfiato e
di acqua potabile, il sistema di drenaggio deve essere collegato mediante un adeguato dispositivo di non ritorno. - Tutte le connessioni dei servizi per la macchina devono rispettare tutte le normative e pratiche locali applicabili. - Il fabbricante si riserva il diritto di apportare modifiche al prodotto che possono non essere riportate nel disegno. -Il condotto di scarico a cui si allacciano le macchine non deve presentare ostruzioni o sifoni
- The machine shall be horizontally levelled. - The electrical supply of each machine must be protected with a ground fault interrupter (30 mA, "AC" type). - Manual shut off valves are required adjacent to supply connection points for all media. - For all ducted exhausts prevent condensate backflow into the machine. Pitch vent ducting and discharge condensate at lowest point. - If a steam condenser is supplied and connected to a potable water supply, the machine should be connected to the drainage system using a proper non-return device. - All services connections to the machine must comply with all applicable local codes and practices. - The manufacturer reserves the right to make product changes that may not be reported in the drawing. -The drain duct to which machines are connected has not be clogged or be equipped with siphon
107 daN (kg) 127 daN (kg) 114 daN (kg)
ACCESSORI INSTALLATI - OPTIONALS INSTALLED NESSUNO - NONE
Dimensioni imballo macchina Machine package dimensions: A= 670 mm B= 650 mm C= 1500 mm D= 686 mm E= 650 mm F= 115mm G= 1615 mm
05
13-12-2013
CHANGING DIMENSIONS
Lupo V.
Capovilla I.
04
14/11/2013
CORRETTO STAFFA FISSAGGIO A MURO - CORRECT WALL BRAKET
Berton A.
Capovilla I.
Rev.
Data / Date
Descrizione / Description
Dis./Drawn
A3
MD04#42 Rev.00
Descrizione/Description:
DISPOSIZIONE GENERALE / GENERAL ARRANGEMENT Modello / Model:
Il presente documento di proprieta' della STEELCO spa, esso costituisce un bene di rilevante valore economico e non puo' essere trasmesso e comunque divulgato a terzi senza specifica autorizzazione scritta della Direzione STEELCO. This document is the property of STEELCO spa, it is an asset of considerable economic value and can not be transmitted and otherwise divulged to third perties without specific written permission of the Directorate STEELCO.
GA_xxxxxxxxxxx Data / Date:
BP 100 HSER (5,25kW 400V 50Hz - XXE version) Codice cliente / Customer code:
--
Approv. Foglio/Sheet:
Progetto / Project:
STANDARD
Ingegneria / Engineering:
STEELCO
12/12/2013
1/1
Rev. / Rev.: Scala / Scale:
05
1:15
Rif. ordine / Order ref.:
--
--