EXTRACT EXTRACT DISCHARGESUPPLY INTAKE INTAKE ELECTRICHEATER Legend Extract grille Supply diffuser Attenuator Cross talk attenuator Fire/Smoke damper ...
11 downloads
18 Views
661KB Size
Notes
01
02
01
A
03
04
3
02
4
05
5
1.
This drawing shall be read in conjunction with all other services, Architectural drawings, project specifications and contract documentation.
2.
All grilles and diffusers to have opposed blade dampers.
3.
All ductwork to DW144/DW172 (where applicable).
4.
Flex to be used only straight-all bends to be rigid.
5.
Fire dampers to be located in accordance with fire strategy drawing requirements.
6.
Access doors to be located adjacent to fire dampers and every 3m.
7.
All branch connections shall have VCD's.
8.
All diffusers and grilles to be supported by structure.
9.
In positions of restricted headroom, ducts may be supported with flat bar formed to duct shape with fixings at sides on bent lugs.
10.
All ductwork brackets to have an acoustic soft rubber or neoprene interface layer to the duct.
11.
All supply ductwork, including supply plenum boxes to be thermally insulated.
12.
All references to specific manufacturers are made for design specification purposes, installed equipment should be of equal standard and approved.
13.
All Heat Recovery Units to be fitted with 22mm condensate drains.
14.
All louvres to be 50% free area.
6
6
03
04
05
06
3
4
5
6
A
A
Legend B
B
B
B
B
EG01
Supply ductwork Extract ductwork
Corridor ??
SG01
Toilet extract ductwork
0.23 ?? 250ø AC01
This room layout is indicative and is subject to change. C
C
C
D
D
EG02
Vacant ?
350ø 001 350ø
E
250øSG02 VCD
250ø
C
Toilet?VCD man Toilet 250ø ? woman EF01 VCD 005150ø
150ø
VCD
D EE
600x300 External Louvre
0.25 ?
200ø VCD
Attenuator Cross talk attenuator Fire/Smoke damper
VCD 150ø
Volume control damper
EXTRACT
SUPPLY
EXTRACT
Supply diffuser C
MALE200ø TOILETS 0.37 ?
VCD
E
350ø
ACCESSIBLE ? TOILET Restroom disabled 004 ? Room TEG02 150ø 0.41 G380
150ø VCD
350ø
Extract grille
STORE Kitchenette ? 003 TEG01 0.40 ?
CONFERENCE
0.38 ? E
VCD AC02
ELECTRIC HEATER
F INTAKE
AC03 EG03
HRU01 DISCHARGE
F
INTAKE
F
TEG03 ?Storage TEG04 TEG05 TEG06 TEG07 AC04 SG03
350ø
350ø
VCD
F
F
? 0.26 CORRIDORCORE 1 ? 008 007Staircase 0.39 ?
G
G H
G H
G H
G
800x400 External Louvre
800x400 External Louvre
01
02
1
2
1
2
03
04
05
06
C3
SS
05.06.17
Louvre Sizes Added.
C2
SS
05.05.17
Fan and Grille References Added.
C1
FR
11.04.17
Ventilation Design Updated Inline with Layout.
project
Moxy Heathrow
title
Proposed Ventilation Layout Ground Floor Sheet 1 of 3
scale
Key Plan
date 22.11.2016
drawing no. PA1064
M-301
rev. C3