NOTES 1, CABLES TO BE, INSTALLED, GLANDED & IDENTIFIED BY ELECTRICAL SUB CONTRACTOR, INTERNAL CONNECTIONS WITHIN CONTROLLERS BY SE CONTROLS AT COMMISSIONING STAGE PERMANENT MAINS POWER IS REQUIRED AT COMMISSIONING STAGE.
A
EF:01 DUTY
EF:02 STAND-BY
2, EACH MANUAL CONTROL POINT AND KEY SWITCH REQUIRES A 47MM DEEP SINGLE FLUSH BACK BOX SUPPLIED AND FITTED BY OTHERS. ALLOW 150MM GAP BELOW ALL MCP'S FOR ACTIVATION/RESET KEY USE.
B
DIVERSE INCOMING FAN SUPPLIES 400v / 3ph / 50Hz MOTOR RATED WITH INVERTOR STARTING @29A (4 CORE + EARTH FP600 BY OTHERS)
G
3, WIRING TO BE INSTALLED TO COMPLY WITH BS8519. WE RECOMMEND THE INSTALLATION OF FP200 GOLD FOR CATEGORY 1 INSTALLATIONS AND FP PLUS FOR CATEGORY 3 INSTALLATIONS.
H FAN CONTROL PANEL
A = 2 CORE + EARTH X 2.5MM² FP PLUS BY OTHERS B = 5 CORES X 1.5MM² FP PLUS BY OTHERS C = 3 CORE + EARTH X 1.5MM² FP PLUS BY OTHERS D = 4 CORE + EARTH X 2.5MM² FP PLUS BY OTHERS E = NOT USED F = 4 CORE + SCREEN X 1.5MM² FP PLUS BY OTHERS G = 3 CORE + EARTH FP600 BY OTHERS TO BE SIZED ACCORDINGLY H = 4 CORE + EARTH FP600 BY OTHERS TO BE SIZED ACCORDINGLY I = 2 CORE + EARTH X 1.5MM² LSF/PVC CABLE BY OTHERS J = 3 CORE + EARTH X 1.5MM² LSF/PVC CABLE BY OTHERS K = 2 CORE + EARTH X 1.5MM² FP PLUS BY OTHERS
STANDBY FAN ACTIVATED FAULT POWER
C
JB
TEST SWITCH
JB
JB
ROOF A
A
F D
A
EF:01 DUTY
D
SHEVTEC CONTROL PANEL
N/C FAI
N/C FAI
D
E
SHEVTEC CONTROL PANEL
365 X 338 X 128
N/C FAI
ROOF LOUVRE VENT
365 X 338 X 128 JB
C
B
B
5A
5A
C F
ZONE 8
FAN CONTROL PANEL
5A
N/O FAI
C
ZONE 7
K
G
LVL 6
PS 0-10V
B
LVL 5
N/O FAI
PS 0-10V
B
D
LVL 4
N/O FAI
PS 0-10V
D
K
LVL 2
N/O FAI
PS 0-10V
K
LVL 1
TAMPERPROOF MANUAL CONTROL POINT @ 1800MM FROM FFL
N/O FAI
AUTO / BOOST
C D
JB
230V 5AMP UNSWITCHED FUSED SPUR BY OTHERS
F
L
D
M. H AWAS
C
M. H AWAS
B
Amended By.
C
N/O FAI
JPB
CABLING AMENDED , FIRE ZONES ADDED, INTERFACES AMENDED ADDED FIRE ALARM INTERFACE TO OS2 PANELS CHANGE THE SUP PLY, LOUVERS, SMOKE DETECTORS TO FAI AND CABLE S,ADDED MCPs TO 7TH FLOOR & ADDITIONAL STAIR CORE AND RISE R
A
AUTO / BOOST
PS 0-10V
ZONE 1
5A
DRAWING REVISION DETAILS
PS 0-10V
JB
K
VOLT FREE CONTACT FROM FIRE ALARM BY OTHERS (N/O - NORMALLY OPEN, N/C NORMALLY CLOSED) J
C
ZONE 2
FAI AUTO / BOOST
D
JB
K
I
AUTO / BOOST
C
ZONE 3
CORRIDOR PRESSURE SENSOR
PS 0-10V
NON TAMPERPROOF MANUAL CONTROL POINT COMPLETE WITH FINGER PLATE @ 1800MM FROM FFL
PS 0-10V
F
D
JB
J
N/O FAI
H
FAN KEY SWITCH
B
C
ZONE 4
LVL 3
B
AUTO / BOOST
JB
K
SHEVTEC DAMPER
C
ZONE 5
I
G
OSLOOP COORDINATOR 411mm X 305mm X 121mm (H x W x D)
AUTO / BOOST
JB
K
365 X 338 X 128
C
ZONE 6
K
SHEVTEC CONTROL PANEL HxWxD
SHEVTEC CONTROL PANEL
AUTO / BOOST
D
JB
H
P OW ER
AUTO / BOOST
D JB
N/O FAI
F
FAU LT
TEST SWITCH
PS 0-10V
ZONE 9
365 X 338 X 128
FAN CONTROL PANEL
S TAN DBY FAN AC TIVATED
ZONE 11
ZONE 10
SHEVTEC CONTROL PANEL
C
SHEVTEC DUTY STANDBY FAN SET
F E
B
EF:02 STAND-BY
F
LVL 7
A
FIRST ISSUE Revision/Issue
No.
A.P
07.07.17
A.P
13-06-17
A.P
01-06-17
MC
19.05.17
Checked By.
Date
K
CUSTOMER
CORDANT SERVICES PROJECT
AUTO / OFF
L
MOXY HOTEL STRATFORD
K
DRAWING STATUS
5A x M
LVL G
D
PRELIMINARY (NOT FOR CONSTRUCTION
FOR APPROVAL
FOR CONSTRUCTION
AS BUILT
DRAWING No.
M
16079-E-001
SHAFT
LOBBY
ENTRANCE
RISER
FIRE FIGHTING STAIR
MEANS OF ESCAPE STAIRS
MEANS OF ESCAPE STAIRS
CORE 1
CORE 2
CORE 3
DRAWING TITLE
SMOKE VENTILATION SCHEMATIC DRAWN BY: SP/SC
DATE:
SCALE
19.05.17
NTS
SHEET SIZE
A3
Lancaster House, Wellington Crescent Fradley Park, Lichfield Staffordshire, WS13 8RZ Tel: 01543 443060 E-mail: