E E E vcd vcd vcd FCU FCU vcd FCU FCU vcd vcd vcd vcd FCU A B C D E F G H I K L M N O 1 2 3 4 5 6 7 8 200 x 1150 x 620 FCU FCU M.2 620 x 620 x 306 FCU...
10 downloads
14 Views
416KB Size
General Notes This drawing to be read in conjunction with all standard details and specifications. All dimensions to be verified on site. All works to comply with current building regulations.
NOTES: 1.
REFER TO STANDARD & PARTICULAR SPECIFICATIONS.
2.
ALL FIRE DAMPERS (FD) TO HAVE DUCT ACCESS PANEL.
3.
FINAL POSITION OF AP'S TO BE CUT IN AFTER INSTALLATION
VENTILATION LEGEND 2
1
3
4
5
400 x 400 DUCT TA CONNECTS TO KEF4 ON ROOF ABOVE
6
7
8
CEILING MOUNTED EXTRACT GRILLE
REFRIGERANT PIPEWORK
SEE BRITANNIA DRAWINGS FOR CANOPY DETAILS
2 PIPE REFRIGERANT
CEILING MOUNTED EXTRACT GRILLE
LINEN ROOM EXTRACT (200 x 200) T/A
250 x 250 WASHUP EXTRACT FROM CANOPY
A
CEILING MOUNTED SUPPLY GRILLE
FIRE FIGHTING CORE SMOKE EXTRACT DUCT 600Ø. REFER TO INTERACTIVE SPECIAL PROJECTS DESIGN
SMOKE FIRE DAMPER
250 x 200
130Ø CHP FLUE 250Ø GENERATOR FLUE FROM B2 PLANTROOM TERMINATE AT ROOF LEVEL
300x300 E
300x300 400x400 3 PIPE REFRIGERANT TO H/L, RUN AGAINST WALL CLIPPED TO CABLE TRAY
VCD - VOLUME CONTROL DAMPER
HEADER DUCT
HEADER DUCT
FIREMANS SMOKE CONTROL SYSTEM OVERRIDE PANEL
400x300
KEF1
REFER TO DRAWING No. COR-217-MEP-PLN-002 FOR PLANT LAYOUT IN THIS AREA
FAN COIL UNIT A - 1150(l) x 620(w) x 200(h)
FCU B
FAN COIL UNIT B - 750(l) x 620(w) x 200(h)
FCU C
FAN COIL UNIT C - 950(l) x 620(w) x 200(h)
FCU D
FAN COIL UNIT D - 750(l) x 200(w) x 620(h) FLOOR MOUNTED
EG 7/1 CLEANER
400x300
FCU A
620 x 620 x 306 FCU FCU M.7
OUTLINE OF CEILING FEATURE. SEE ARCHITECT'S LAYOUT FOR EXACT LOCATION & DIMENSIONS.
KEF2
KITCHEN
600 X 600 SUPPLY AIR DUCT FROM SF2 ON ROOF ABOVE. DUCT MOUNTED HEATER HB7/1 WITH HR1 PIPEWORK FROM ROOF BOILER PLANTROOM SUPPLY AIR GRILLES IN CEILING 2 x SG7/8
150 x 150 WC EXTRACT F/B TO H/L CONENCTS TO BEF3 WITH HORIZONTAL EXHAUST. BEF3/RS & BEF3/AS
LSV LOBBY SMOKE VENTILATOR AUTOMATIC DOOR
WC
STAIR S01
500x500
OPEN PLANT AREA
125ø
LIFT L3
500 x 500 EXTRACT DUCT T/A CONNECTS TO KEF5 ON ROOF ABOVE
CORRIDOR
500 x 250 AIR TRANSFER GRILLE ABOVE CEILING
WC LOBBY
450 x 450 ACCESS PANEL FOR BSV BOX (TYP.)
B
FAN COIL UNIT A.1 - A.4 - 1150(l) x 620(w) x 200(h) FAN COIL UNIT A.6 - 700(l) x 620(w) x 200(h) FAN COIL UNIT B.1 - B.3 - 950(l) x 620(w) x 200(h) FAN COIL UNIT B.4 - 700(l) x 620(w) x 200(h) FAN COIL UNIT C.1 - C.2 - 950(l) x 620(w) x 200(h) FAN COIL UNIT D.1 - D.5 - 1150(l) x 620(w) x 200(h) FAN COIL UNIT M.1 - M.6 - 1150(l) x 620(w) x 200(h) FAN COIL UNIT 0.06 - 0.07 - 950(l) x 620(w) x 200(h)
FCU
WC
OUTLINE OF CEILING FEATURE. SEE ARCHITECT'S LAYOUT FOR EXACT LOCATION & DIMENSIONS. SEE NOTE *
RA 7/6
VRF BRANCH SELECTOR BOX 388(l) x 326(w) x 207(h)
E E
REFRIGERANT 3 PIPES CLIPPED TO CABLE TRAY
300 x 250
WC
C
E
vcd
200ø vcd
200 x 1150 x 620 FCU FCU M.2
F
FCU
FCU
vcd
200ø
125ø
WC
50mm LINEAR SLOT DIFFUSER 100mm LINEAR SLOT DIFFUSER
ACC. WC
FCU
EXTRACT FAN IN CEILING VOID 278 (l) X 259 (w) X 259 (h) - BEF4
125ø
200 x 1150 x 620 FCU M.4
FCU
RA 7/1
BEF1
EXTRACT FAN LOCATED IN CEILING VOID. 394(l) X 300(w) X 184(h) TEF - 2
SG 7/7 FCU
200 x 1150 x 620 FCU M.3
vcd
200ø
200ø
vcd
250ø
RA 7/5
4-WAY BLOW CASSETTE 950(l) x 950(w) x 306(h) 950(l) x 950(w) x 264(h)
100 X 150 LOUVRE TEF2/AS
SEF4
RESTAURANT
900 X 900 ACCESS PANEL FOR FCU (TYP.)
600 x 600 ACCESS PANEL
200ø
E
vcd
700 x 350 SUPPLY FA
125ø
RA7/3
200Ø
7/AHU8S/RS
vcd
D
4-WAY BLOW CASSETTE 620(l) x 620(w) x 306(h) vcd
200Ø SUPPLY DUCT
SG 7/2
SG 7/3
200 x 1150 x 620 FCU M.5
RA 7/2
RAS1 800 x 100 RETURN AIR SLOT IN CEILING 0.075m2
RAS2
RAS2 900 x 150 RETURN AIR SLOT IN CEILING 0.120m2
250 x 250 WC EXTRACT F/B TO H/L CONNECT TO BEF4 WITH HORIZONTAL EXHAUST. BEF4/RS & BEF4/AS
200 x 1150 x 620 FCU M.6
SG 7/5
RAS1
CABLE TRAY LEGEND
SG 7/6
RA 7/4
SKYLIGHT
KEF3
REFRIGERANT PIPEWORK CABLE TRAY 300mm
G OUTLINE OF CEILING FEATURE. SEE ARCHITECT'S LAYOUT FOR EXACT LOCATION & DIMENSIONS.
H
FD. ACCESS PANELS REQUIRED.
I NOTES: 1. SETTING OUT DIMENSIONS FOR ACCESS PANELS FOR FAN COIL UNITS/ CASSETTE UNITS, FANS, BSV BOXES, HEATER BATTERIES, FIRE DAMPERS & DOOR HEATER WILL BE DETERMINED FROM THE FINAL INSTALLATION POSITION OF THESE UNITS. SITE TO CONFIRM EXACT POSITIONS. 2. ACCESS PANEL FOR CASSETTE UNITS TO BE ON THE DRAIN, POWER UNIT & REFRIGERANT SIDE. SITE TO CONFIRM THE SERVICES SIDE ONCE INSTALLED.
ROOF TERRACE
3. ACCESS PANEL FOR BSV BOXES TO BE ON THE CONTROL BOX SIDE. SITE TO CONFIRM CONTROL BOX SIDE ONCE INSTALLED.
K
SUPPLY DIFFUSERS & EXTRACT GRILLES POSITIONS TO BE CONFIRMED & APPROVED. 350 x 350 WC EXTRACT F/B TO L/L
L
M
CEILING ACCESS PANELS REQUIRED FOR FCU UNITS. LOCATION TO BE DETERMINED FROM ARCHITECT'S CEILING PLAN. ACCESS PANEL POSITIONS FOR FCU'S AND BS BOXES.
A4
A3
DUCTWORK FROM FCU UNITS M2,3,4, & 5 REVISED.
Model
SLC
21-09-17
GRILLES SG7/2, 7/3, 7/5, 7/6 & 7/7 REVISED. RA 7/1 - 7/6
Engineer
RS
21-09-17
SHOWN. FCU M1 & GRILLES SG 7/1, 7/4 REMOVED.
Checked
RS
21-09-17
DUCTWORK REVISED TO KITCHEN CANOPY.
Model
FCU REPOSITIONED TO CEILING GRID. BEF 2 AND
Engineer
ATTENUATORS REVISED. SEF4 REPOSITIONED.
Checked
PLANT BEF2 REVIEW NOTE.
Model
SLC
05-05-17
RESTAURANT UNDER REVIEW.
Engineer
RS
05-05-17
Checked
RS
05-05-17
Model
SLC
29-03-17
Engineer
RS
29-03-17
Checked
RS
29-03-17
Model
SLC
23-02-17
Engineer
RS
23-02-17
Checked
RS
ACCESS PANELS ADDED. NOTE ADDED.
A2
GREEN ROOF
FOR CONSTRUCTION APPROVAL
A1
NEW POSITION LOCATION OF PLANT UNDER REVIEW BY ARCHITECT STAIR S02
Rev
Description
23-02-17
Init
Date
TEF2/AS
TEF2/RS
CONTRUCTION APPROVAL
N BEF2 ( 2 No. GIGABOX 500 EC) 150 x 150 WC EXTRACT F/B TO L/L
TEF2/RS
TEF2/AS BEF2
ORIGINAL POSITION
Cordant Projects Portland Road, Oak Green Earl Road, Stanley Green Business Park Cheadle Hulme, Cheshire. SK8 6QL (T) 0161 641 4941
TWIN FAN - BEF2
Client
FR HOLDINGS LTD. O
Project/Site Location
GARLICK HILL, EC4
Drawing Title
SEVENTH FLOOR VENTILATION LAYOUT
Scale
1 : 50 Sheet Size
A0
Modelled
Engineer
Approved
PH
RS
RS
Drawing No.
COR-217-MV-PLN-010
Date
Oct'16 Revision
A4